background image

Checkout = HEAT PUMP HEATING

HIGH HEAT RUNTIME: 5 min.

LOW HEAT RUNTIME: 5 min.

DEFROST: NO

The heat pump heating mode can be exercised with this menu
option. With a 2-speed heat pump, a low heat runtime and a high
heat runtime are independently selectable to exercise. A defrost
cycle is also selectable. Default time = Fixed 5 min. minimum,
range = 5 - 120 min.

Checkout = HEAT PUMP COOLING OR AC COOLING

HIGH COOL RUNTIME: 5 min.

LOW COOL RUNTIME: 5 min.

The heat pump cooling mode (or AC cooling mode) can be
exercised with this menu option. With a 2-speed heat pump or AC
unit, a low cool runtime and a high cool runtime are independently
selectable to exercise. The display will change to show the heat
pump or AC operating status. Default time = Fixed 5 min.
minimum, range = 5 - 120 min.

Checkout = HUMIDIFIER

ON

OFF

The humidifier can be exercised On and Off with this menu option.

Checkout = VENTILATOR

The ventilator can be exercised through all of its operating speeds
with this menu option.

SERVICE MENUS

The Service Info menu will only show the equipment installed in
the system. Below is a sample using a furnace and a dual fuel heat
pump. A sample service menu is shown in Fig. 25.

Service = FURNACE STATUS

The Status screens will show all of the current operating param-
eters of each installed piece of equipment.

HEAT STAGE:

OFF, LOW, HIGH

Displays stage of heat that the furnace is currently delivering.

AIRFLOW CFM:

(furnace model dependent)

Cubic Feet per Minute of air the blower is currently delivering.

INDUCER RPM (90% furnaces only):

Inducer motor RPM value.

BLOWER RPM:

Blower motor RPM value.

STATIC PRESS:

Inches of water. Displays static pressure that the furnace is
currently experiencing.

LOCKOUT TIMER:

Seconds

If a lockout timer is active, this will show the current time value.
See furnace manual for details on lockout timers.

Service = FAN COIL

ELECTRIC HEAT STATUS:

OFF, LOW, MED, HIGH

Displays stages of electric heat that the fan coil is currently
delivering.

AIRFLOW CFM:

(fan coil model dependent)

Cubic Feet per Minute of air the blower is currently delivering.

BLOWER RPM:

Blower motor RPM value

STATIC PRESS:

Inches of water

Displays static pressure that the fan coil is currently experiencing.

Service = HEAT PUMP / AC STATUS

STAGE: (HEAT / COOL):

OFF, LOW, HIGH

Displays stage of heating or cooling that the heat pump/AC is
delivering.
DEFROST:

NO, YES

Displays status of defrost mode if heat pump.

AIRFLOW CFM:

Indoor unit cfm measurement.

BLOWER RPM:

RPM feedback from indoor motor.

COIL TEMP:

Degrees F.

Temperature of the outdoor unit coil (only available on 2-speed
communicating outdoor units).

STATIC PRESS:

Static pressure of indoor unit.

Service = LAST 10 SYSTEM FAULTS

This screen will show last 10 faults that occurred throughout the
system. Each fault has the time and date of incident recorded.
Service technician should enter current date in

TODAY’S

DATE

menu section before checking and logging the last 10

system faults. Each fault has a two-letter acronym preceding the
fault name to identify which piece of equipment generated the
fault.

HP = heat pump

AC = air conditioner

FN = furnace

FC = fan coil.

Service = RUN / FAULT HISTORY

The indoor unit and outdoor unit (if communicating) has the
following histories:

NOTE:

For Critical Fault Screens, see Trouble Shooting section

in this document.

Resettable Faults:

Fault counters for each piece of equipment that can be reset.

Cycle Counters:

Number of heat/cool/power cycles the unit has performed.

Fig. 25 — SERVICE INFO MENUS

A03205

SERVICE INFO

FURNACE STATUS
HEAT PUMP STATUS
LAST 10 SYSTEM FAULTS
RUN/FAULT HISTORY
TODAY’S DATE
MODEL/SERIAL NUMBER
SERVICE PHONE NUMBER

   BACK               SELECT

—10—

Summary of Contents for Evolution Control SYSTXBBUID01

Page 1: ...rmo stat plus much more and a variable speed furnace or FE fan coil They support controlled ventilation humidification dehumidifica tion and air quality control Either a two speed communicating or a standard 24 vac controlled outdoor unit may be used When using conventional outdoor units the variable speed furnace or fan coil provides the 24 volt signals needed to control them Also the Evolution N...

Page 2: ...WG or larger NOTE ABCD bus wiring only requires a four wire connection however it is good practice to run thermostat cable having more than four wires in the event of a damaged or broken wire during the installation Each device in the Evolution System has a four pin connector labeled ABCD It is recommended that the following color code be used when wiring each device A Green Data A B Yellow Data B...

Page 3: ...volution Control mounting plastic recess mount or surface mount and decorative backplate if desired 4 Route wires through large hole in mounting plastic Level rear plastic against wall for aesthetic value only Evolution Control need not be level to operate properly and mark wall through two mounting holes 5 Drill two 3 16 inch mounting holes in wall where marked Fig 4 Surface Mount Backplate A0318...

Page 4: ...perature sensor may be installed not required at the indoor furnace or fan coil OAT terminals When OAT is applied the Evolution System will provide full system features and benefits See wiring diagram Fig 14 for a Typical Connection Diagram for FE fan coil with a 1 speed heat pump using non communicating outdoor unit When OAT is applied the Evolution System will provide full system features and be...

Page 5: ...None no unit installed Press the right side button to continue to the next screen If you have selected either AC or HP as the outdoor unit type the following middle screen will appear See figure 16 Press either Time or Temp buttons to select appropriate Btu size of outdoor unit then press right side button to continue If a NIM Network Interface Module is applied for non communicating two speed out...

Page 6: ...lso after selecting YES if the filter type is not an EAC the indoor unit will operate the blower for one minute to do a system static pressure check QUICK START For first time installers Quick Start will allow you to start up the Evolution System before you have the chance to learn all the details of system operation However for the best possible comfort and operation we recommend that you refer t...

Page 7: ...RVICE MENUS The INSTALL SERVICE menus contain a set of vital information This information enables the Installer or Service person to view a summary of what has been installed etc To enter INSTALL SERVICE menus press and hold the ADVANCED button for at least ten seconds The following menu will appear See figure 20 NOTE The INSTALL SERVICE menu will automatically exit after 60 minutes of no push but...

Page 8: ...ncreased comfort AC AIRFLOW COMFORT default EFFICIENCY MAXIMUM Selects the airflow of the furnace when cooling COMFORT is a decreased airflow used to improve humidity control EFFI CIENCY is the airflow used to meet specified ratings MAXI MUM is a fixed airflow speed of 400 CFM ton based on the outdoor unit size DEHUM AIRFLOW NORMAL default HIGH NORMAL airflow adjustment is used during dehumidifyin...

Page 9: ...turn on SETUP UV LIGHTS UV LIGHTS INSTALLED NO YES If YES indicates to the system whether UV lights are installed CHANGE INTERVAL 6 to 48 months operation time default 12 months Interval at which the Change UV Lights notification will be displayed SETUP SYSTEM MAINTENANCE REMIND OWNER OF ROUTINE MAINTENANCE EVERY This setup is used to adjust the timer interval in which the normal System Maintenanc...

Page 10: ...lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service FAN COIL ELECTRIC HEAT STATUS OFF LOW MED HIGH Displays stages of electric heat that the fan coil is currently delivering AIRFLOW CFM fan coil model dependent Cubic Feet per Minute of air the blower is currently delivering BLOWER RPM Blower motor RPM value STATIC PRESS Inches of w...

Page 11: ...e equipment is not cycled more than the selected times per hour This timer is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan and Temp buttons Ten Minute Staging Timer In multistage heating or cooling this timer prevents any higher stage from turning...

Page 12: ...l fuel Code 41 Blower Motor Fault USER INTERFACE No communication with indoor unit SYSTEM MALFUNCTION SCREEN The following errors will cause a System Malfunction Screen to pop up FAN COIL Code 37 Heater output sensed ON when not energized FURNACE Code 13 Limit Circuit Lockout Code 14 Ignition Lockout Code 21 Gas Heating Lockout Code 22 Abnormal Flame Proving Signal dual fuel only Code 23 Pressure ...

Reviews: