background image

SETUP = THERMOSTAT:

AUTO MODE SETUP:

Enable/Disable Auto Changeover mode (default=Enable).

Auto Changeover Time may be adjusted 5 to 120 minutes,
(default = 30 minutes).

When Auto mode is enabled (factory default) a change from heat
to cool (or vice versa) will not occur until an opposite mode
demand has existed for 30 minutes. If the set point is changed, the
30 minute timer is deleted.

HEAT/COOL DEADBAND:

0 to 6 degrees, (default = 2°).

A minimum difference of 2° is enforced between heating and
cooling desired temperatures. This will allow one setting to

push

the other to maintain this difference.

OFFSETS: This option allows calibration (or deliberate miscali-
bration) of the temperature and humidity sensors. These offsets are
added to the actual temperature/humidity values (defaults = 0).

Room Temp Offset: -5 to +5 degrees.

Outside Temp Offset: -5 to +5 degrees.

Humidity Offset: -10 to +10 percent.

CYCLES PER HOUR:

Maximum cycles per hour = 4 (default) or 6.

Anticipator = 1 to 9 (default=3).

PROGRAMMING:

On or Off (default=On)

Periods Per Day = 2 or 4 (default=4)

Programmable Fan On/Off (default=Off)

SMART RECOVERY:

On or Off, (default=On)

Applies to programmable operation only. Will start recovery 90
minutes prior to schedule change in both heating and cooling.

ENGLISH/METRIC DISPLAY:

°F or °C, (default = °F)

RESET FACTORY DEFAULTS:

Program Schedule:

Yes/No to reset back to Energy Star defaults.

User Settings:

Yes/No to reset the user settings in the Advanced Setup.

Install Settings:

Yes/No to reset install settings in Install/Service menus.

SETUP = FURNACE:

Upon a first time start-up of the Evolution Control™, the furnace
dip switch settings will be copied to the furnace setup menu. Any
changes can then be made from the Evolution Control™.

AIRFLOW:

COMFORT (default)

EFFICIENCY

Selects the airflow of the furnace when heating. EFFICIENCY is
the airflow used to meet specified ratings, COMFORT is a
decreased airflow used to increase the output air temperature and
provide increased comfort.

AC AIRFLOW:

COMFORT (default)

EFFICIENCY

MAXIMUM

Selects the airflow of the furnace when cooling. COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY 
is the airflow used to meet specified ratings. MAXI-
MUM 
is a fixed airflow speed of 400 CFM/ton based on the
outdoor unit size.

DEHUM AIRFLOW:

NORMAL (default)

HIGH

NORMAL airflow adjustment is used during dehumidifying. If
duct sweating is an issue, selecting HIGH will increase the
dehumidifying airflow speed and reduce the sweating.

LOW HEAT RISE:

ON

OFF (default)

Set this to ON if the system contains a bypass humidifier. The ON
setting will increase the furnace low heat airflow.

STAGING:

SYSTEM (default)

FURNACE

LOW

HIGH

Controls the staging of the furnace. SYSTEM setting will allow
the Evolution Control™ to determine furnace staging. FURNACE
will allow the Furnace algorithm to control staging. LOW will
only run the low stage of furnace heat. HIGH will only run the
high stage of furnace heat.

OFF DELAY:

90 seconds (default)

120 seconds

150 seconds

180 seconds

Amount of time the blower will continue to run after heating has
shut off.

LOCKOUT TEMP:

NONE (default)

+5 to 55 deg F

Appears on dual fuel systems only (furnace with heat pump).
Outside temperature above which the furnace will NOT run.

SETUP = FAN COIL:

HP/AC AIRFLOW:

COMFORT (default)

EFFICIENCY

MAXIMUM

Selects the airflow of the fan coil when heating or cooling with a
heat pump (or cooling with an AC unit). COMFORT is a
decreased airflow used to improve humidity control. EFFI-
CIENCY 
is the airflow used to meet specified ratings. MAXI-
MUM 
is a fixed airflow speed of 400 CFM/ton based on the
outdoor unit size.

DEHUM AIRFLOW:

NORMAL (default)

HIGH

Normal airflow adjustment used during dehumidifying. If duct
sweating is an issue, selecting HIGH will increase the dehumidi-
fying airflow speed and reduce the sweating.

HEATER SIZE:

(choices dependent upon fan coil model)

This will show the heater size entered during the start-up process.
This value can be changed to another value (limited by the model
of the fan coil). If the electric heater is self-identifying, this value
is not shown.

—8—

Summary of Contents for Evolution Control SYSTXBBUID01

Page 1: ...rmo stat plus much more and a variable speed furnace or FE fan coil They support controlled ventilation humidification dehumidifica tion and air quality control Either a two speed communicating or a standard 24 vac controlled outdoor unit may be used When using conventional outdoor units the variable speed furnace or fan coil provides the 24 volt signals needed to control them Also the Evolution N...

Page 2: ...WG or larger NOTE ABCD bus wiring only requires a four wire connection however it is good practice to run thermostat cable having more than four wires in the event of a damaged or broken wire during the installation Each device in the Evolution System has a four pin connector labeled ABCD It is recommended that the following color code be used when wiring each device A Green Data A B Yellow Data B...

Page 3: ...volution Control mounting plastic recess mount or surface mount and decorative backplate if desired 4 Route wires through large hole in mounting plastic Level rear plastic against wall for aesthetic value only Evolution Control need not be level to operate properly and mark wall through two mounting holes 5 Drill two 3 16 inch mounting holes in wall where marked Fig 4 Surface Mount Backplate A0318...

Page 4: ...perature sensor may be installed not required at the indoor furnace or fan coil OAT terminals When OAT is applied the Evolution System will provide full system features and benefits See wiring diagram Fig 14 for a Typical Connection Diagram for FE fan coil with a 1 speed heat pump using non communicating outdoor unit When OAT is applied the Evolution System will provide full system features and be...

Page 5: ...None no unit installed Press the right side button to continue to the next screen If you have selected either AC or HP as the outdoor unit type the following middle screen will appear See figure 16 Press either Time or Temp buttons to select appropriate Btu size of outdoor unit then press right side button to continue If a NIM Network Interface Module is applied for non communicating two speed out...

Page 6: ...lso after selecting YES if the filter type is not an EAC the indoor unit will operate the blower for one minute to do a system static pressure check QUICK START For first time installers Quick Start will allow you to start up the Evolution System before you have the chance to learn all the details of system operation However for the best possible comfort and operation we recommend that you refer t...

Page 7: ...RVICE MENUS The INSTALL SERVICE menus contain a set of vital information This information enables the Installer or Service person to view a summary of what has been installed etc To enter INSTALL SERVICE menus press and hold the ADVANCED button for at least ten seconds The following menu will appear See figure 20 NOTE The INSTALL SERVICE menu will automatically exit after 60 minutes of no push but...

Page 8: ...ncreased comfort AC AIRFLOW COMFORT default EFFICIENCY MAXIMUM Selects the airflow of the furnace when cooling COMFORT is a decreased airflow used to improve humidity control EFFI CIENCY is the airflow used to meet specified ratings MAXI MUM is a fixed airflow speed of 400 CFM ton based on the outdoor unit size DEHUM AIRFLOW NORMAL default HIGH NORMAL airflow adjustment is used during dehumidifyin...

Page 9: ...turn on SETUP UV LIGHTS UV LIGHTS INSTALLED NO YES If YES indicates to the system whether UV lights are installed CHANGE INTERVAL 6 to 48 months operation time default 12 months Interval at which the Change UV Lights notification will be displayed SETUP SYSTEM MAINTENANCE REMIND OWNER OF ROUTINE MAINTENANCE EVERY This setup is used to adjust the timer interval in which the normal System Maintenanc...

Page 10: ...lockout timer is active this will show the current time value See furnace manual for details on lockout timers Service FAN COIL ELECTRIC HEAT STATUS OFF LOW MED HIGH Displays stages of electric heat that the fan coil is currently delivering AIRFLOW CFM fan coil model dependent Cubic Feet per Minute of air the blower is currently delivering BLOWER RPM Blower motor RPM value STATIC PRESS Inches of w...

Page 11: ...e equipment is not cycled more than the selected times per hour This timer is adjustable from 4 to 6 cycles per hour This timer is defeated for one cycle when the desired temperature is manually changed It can also be defeated for one cycle by simultaneously pressing the Fan and Temp buttons Ten Minute Staging Timer In multistage heating or cooling this timer prevents any higher stage from turning...

Page 12: ...l fuel Code 41 Blower Motor Fault USER INTERFACE No communication with indoor unit SYSTEM MALFUNCTION SCREEN The following errors will cause a System Malfunction Screen to pop up FAN COIL Code 37 Heater output sensed ON when not energized FURNACE Code 13 Limit Circuit Lockout Code 14 Ignition Lockout Code 21 Gas Heating Lockout Code 22 Abnormal Flame Proving Signal dual fuel only Code 23 Pressure ...

Reviews: