31
Table 5 – RTU Open Controller Inputs and Outputs
POINT NAME04
BACnet OBJECT
NAME
TYPE OF I/O
CONNECTION PIN
NUMBER(S)
DEDICATED INPUTS
Space Temp / Zone Temp
zone_temp
AI (10K Thermistor)
J20---1 & 2
Supply Air Temperature
sa_temp
AI (10K Thermistor)
J2---1 & 2
Outdoor Air Temperature
oa_temp
AI (10K Thermistor)
J2---3 & 4
Space Temperature Offset Pot
stpt_adj_offset
AI (100K Potentiometer)
J20---3 & 4
Safety Chain Feedback
safety_status
DI (24 VAC)
J1---9
Compressor Safety Status
comp_status
DI (24 VAC)
J1---2
Fire Shutdown Status
firedown_status
DI (24 VAC)
J1---10
Enthalpy Status
enthalpy_status
DI (24 VAC)
J2---6 & 7
Humidistat Input Status
humstat_status
DI (24 VAC)
J5---7 & 8
Zone Temperature
n/a
n/a
J13---1, 2, 3, 4
CONFIGURABLE INPUTS
Indoor Air CO2
iaq
AI (4---20 ma)
J4---2 & 3 or J4---5 & 6
Outdoor Air CO2
oaq
AI (4---20 ma)
Space Relative Humidity
space_rh
AI (4---20 ma)
Supply Fan Status*
sfan_status
DI (24 VAC)
J5---1 or J5---3 or J5---5
Filter Status*
filter_status
DI (24 VAC)
Door Contact Input*
door_contact_status
DI (24 VAC)
Occupancy Contact*
occ_contact_status
DI (24 VAC)
OUTPUTS
Economizer Output
econ_output
AO (4---20ma)
J2---5
Supply Fan Relay State
sfan
DO Relay (24VAC , 1A)
J1---4
Compressor 1 Relay State
comp_1
DO Relay (24VAC , 1A)
J1---8
Compressor 2 Relay State
comp_2
DO Relay (24VAC , 1A)
J1---7
Heat Stage 1 Relay State
heat_1
DO Relay (24VAC , 1A)
J1---6
Heat Stage 2 Relay State
heat_2
DO Relay (24VAC , 1A)
J1---5
Power Exhaust Relay State
pexh
DO Relay (24VAC , 1A)
J11---1 & 3
Perfect Humidity Relay State
dehum
DO Relay (24VAC, 1A)
J11---7, 8
LEGEND
AI
--- Analog Input
AO
--- Analog Output
DI
--- Discrete Input
DO
--- Discrete Output
* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.
The RTU Open controller requires the use of a Bryant
space sensor. A standard thermostat cannot be used with
the RTU Open system.
Supply Air Temperature (SAT) Sensor —
On FIOP--equipped 580J units, the unit is supplied with a
supply--air temperature (SAT) sensor (33ZCSENSAT). This
sensor is a tubular probe type, approx 6--inches (152 mm) in
length. It is a nominal 10--k ohm thermistor.
The SAT is factory--wired. The SAT probe is wire--tied to the
supply--air opening in its shipping position. Remove the
sensor for installation. Re--position the sensor in the flange
of the supply--air opening or in the supply air duct (as
required by local codes). Drill or punch a
1
/
2
--in. hole in the
flange or duct. Use two field--supplied, self--drilling screws
to secure the sensor probe in a horizontal orientation. See
Fig. 40.
Outdoor Air Temperature (OAT) Sensor —
The OAT is factory--mounted in the EconoMi$er2 (FIOP or
accessory). It is a nominal 10k ohm thermistor attached to
an eyelet mounting ring.
SUPPLY AIR
TEMPERATURE
SENSOR
SUPPLY AIR
RETURN AIR
ROOF
CURB
C13783
Fig. 40 -- Mounting Location for Supply Air
Temperature (SAT) Sensor on 580J Units
580J
--
17
--
30
--
V
Summary of Contents for 580J Series
Page 4: ...4 C13745 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit 580J 17 30 V ...
Page 5: ...5 C13747 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit cont 580J 17 30 V ...
Page 6: ...6 C13751 Fig 3 Unit Dimensional Drawing 24 and 28 Size Units 580J 17 30 V ...
Page 7: ...7 C13753 Fig 3 Unit Dimensional Drawing 24 and 28 Size Units cont 580J 17 30 V ...
Page 8: ...8 C13757 Fig 4 Unit Dimensional Drawing 30 Size Units 580J 17 30 V ...
Page 9: ...9 C13759 Fig 4 Unit Dimensional Drawing 30 Size Units cont 580J 17 30 V ...
Page 13: ...13 C09052 Fig 8 Roof Curb Details 17 and 20 Size Units 580J 17 30 V ...
Page 14: ...14 C09100 Fig 9 Roof Curb Details 24 and 28 Size Units 580J 17 30 V ...
Page 15: ...15 C11224 Fig 10 Roof Curb Details 30 Size Unit 580J 17 30 V ...
Page 29: ...29 C13767 Fig 38 RTU Open System Control Wiring Diagram 580J 17 30 V ...
Page 30: ...30 C13768 Fig 39 RTU Open System Control Wiring Diagram with Perfect Humidityt 580J 17 30 V ...
Page 49: ...49 48TC 17 30 V 48TC 17 30 V 48TC 17 30 V 580J 17 30 V ...