11
C
B
D
A
C12384
LOCATION
DIMENSION
CONDITION
A
36---in (914 mm)
• Recommended clearance for air flow and service
B
42---in (1067 mm)
• Recommended clearance for air flow and service
C
18---in (457 mm)
• No Convenience Outlet
• No Economizer
• No field installed disconnect on economizer hood side (Factory---installed disconnect installed).
36---in (914 mm)
• Convenience Outlet installed.
• Vertical surface behind servicer is electrically non---conductive (e.g.: wood, fiberglass).
42---in (1067 mm)
• Convenience Outlet installed.
• Vertical surface behind servicer is electrically conductive (e.g.: metal, masonry).
96---in (2438 mm)
• Economizer and/or Power Exhaust installed.
• Check for sources of flue products with 10 feet (3 meters) of economizer fresh air intake.
D
42---in (1067 mm)
• Recommended clearance for service.
NOTE:
Unit not designed to have overhead obstruction. Contact Application Engineering for guidance on any application planning
overhead obstruction or for vertical clearances.
Fig. 5 -- Service Clearance Dimensional Drawing
Table 1 – Operating Weights
580J*
UNIT LB (KG)
17
20
24
28
30
Base Unit
Novation™ Coil
1824 (829)
1839 (836)
1989 (904)
2118 (963)
N/A
RTPF Coil
1907 (867)
1922 (874)
2072 (942)
2197 (999)
2640 (1200)
Economizer
246 (112)
246 (112)
246 (112)
246 (112)
246 (112)
Powered Outlet
35 (16)
35 (16)
35 (16)
35 (16)
35 (16)
Perfect Humidity™ System
110 (50)
110 (50)
120 (54)
120 (54)
N/A
Curb
14---in/356 mm
240 (109)
240 (109)
255 (116)
255 (116)
255 (116)
24---in/610 mm
340 (154)
340 (154)
355 (161)
355 (161)
355 (161)
580J
--
17
--
30
--
V
Summary of Contents for 580J Series
Page 4: ...4 C13745 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit 580J 17 30 V ...
Page 5: ...5 C13747 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit cont 580J 17 30 V ...
Page 6: ...6 C13751 Fig 3 Unit Dimensional Drawing 24 and 28 Size Units 580J 17 30 V ...
Page 7: ...7 C13753 Fig 3 Unit Dimensional Drawing 24 and 28 Size Units cont 580J 17 30 V ...
Page 8: ...8 C13757 Fig 4 Unit Dimensional Drawing 30 Size Units 580J 17 30 V ...
Page 9: ...9 C13759 Fig 4 Unit Dimensional Drawing 30 Size Units cont 580J 17 30 V ...
Page 13: ...13 C09052 Fig 8 Roof Curb Details 17 and 20 Size Units 580J 17 30 V ...
Page 14: ...14 C09100 Fig 9 Roof Curb Details 24 and 28 Size Units 580J 17 30 V ...
Page 15: ...15 C11224 Fig 10 Roof Curb Details 30 Size Unit 580J 17 30 V ...
Page 29: ...29 C13767 Fig 38 RTU Open System Control Wiring Diagram 580J 17 30 V ...
Page 30: ...30 C13768 Fig 39 RTU Open System Control Wiring Diagram with Perfect Humidityt 580J 17 30 V ...
Page 49: ...49 48TC 17 30 V 48TC 17 30 V 48TC 17 30 V 580J 17 30 V ...