21
Step 10 — Install External Condensate Trap & Line
The unit has one
3
/
4
-in. condensate drain connection on the
end of the condensate pan (see Fig. 21). See Figs. 2, 3 and
4, item “E”, in the view labeled “BACK” for the location of
the condensate drain connection.
STANDARD
SIDE DRAIN
C09056
Fig. 21 -- Condensate Drain Pan Connection
The piping for the condensate drain and external trap can
be completed after the unit is in place. Hand tighten
fittings to the drain pan fitting. Provide adequate support
for the drain line. Failure to do so can result in damage to
the drain pan. See Fig. 22.
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4” (102mm) trap is recommended
MINIMUM PITCH
1” (25mm) PER
10’ (3m) OF LINE
BASE RAIL
OPEN
VENT
TO ROOF
DRAIN
DRAIN PLUG
ROOF
CURB
SEE NOTE
3
˝
(76mm)
MIN
C11291
Fig. 22 -- Condensate Drain Piping Details
All units must have an external trap for condensate
drainage. Install a trap at least 4-in. (102 mm) deep and
protect against freeze-up. If drain line is installed
downstream from the external trap, pitch the line away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do
not use a pipe size smaller than the unit connection
(
3
/
4
-in.).
Step 11 — Make Electrical Connections
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Do not use gas piping as an electrical ground.
Unit
cabinet must have an uninterrupted, unbroken electrical
ground to minimize the possibility of personal injury if
an electrical fault should occur. This ground may consist
of electrical wire connected to unit ground lug in control
compartment, or conduit approved for electrical ground
when installed in accordance with NEC (National
Electrical Code); ANSI/NFPA 70, latest edition (in
Canada, Canadian Electrical Code CSA [Canadian
Standards Association] C22.1), and local electrical
codes.
!
WARNING
NOTE
: Field--supplied wiring shall conform with the
limitations of minimum 63
_
F (33
_
C) rise.
Field Power Supply —
If equipped with optional Powered Convenience Outlet:
The power source leads to the convenience outlet’s
transformer primary are not factory connected. Installer
must connect these leads according to required operation
of the convenience outlet. If an always--energized
convenience outlet operation is desired, connect the
source leads to the line side of the unit--mounted
disconnect. (Check with local codes to ensure this method
is acceptable in your area.) On a unit without a
unit--mounted disconnect, connect the source leads to the
terminal block with unit field power leads. See Fig. 23.
LOAD
SIDE
SEE
DETAIL
A
DETAIL
A
LINE
SIDE
BLK
YEL
BLU
CONTROL BOX
L3
L2
L1
C11181
Fig. 23 -- Location of TB1
Field power wires are connected to the unit at line--side
pressure lugs on the terminal block (see wiring diagram
label for control box component arrangement) or at
factory--installed option non--fused disconnect switch. Use
copper conductors only.
NOTE
: Make field power connections directly to line
connection pressure lugs only.
580J
--
17
--
30
--
V
Summary of Contents for 580J Series
Page 4: ...4 C13745 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit 580J 17 30 V ...
Page 5: ...5 C13747 Fig 2 Unit Dimensional Drawing 17 and 20 Size Unit cont 580J 17 30 V ...
Page 6: ...6 C13751 Fig 3 Unit Dimensional Drawing 24 and 28 Size Units 580J 17 30 V ...
Page 7: ...7 C13753 Fig 3 Unit Dimensional Drawing 24 and 28 Size Units cont 580J 17 30 V ...
Page 8: ...8 C13757 Fig 4 Unit Dimensional Drawing 30 Size Units 580J 17 30 V ...
Page 9: ...9 C13759 Fig 4 Unit Dimensional Drawing 30 Size Units cont 580J 17 30 V ...
Page 13: ...13 C09052 Fig 8 Roof Curb Details 17 and 20 Size Units 580J 17 30 V ...
Page 14: ...14 C09100 Fig 9 Roof Curb Details 24 and 28 Size Units 580J 17 30 V ...
Page 15: ...15 C11224 Fig 10 Roof Curb Details 30 Size Unit 580J 17 30 V ...
Page 29: ...29 C13767 Fig 38 RTU Open System Control Wiring Diagram 580J 17 30 V ...
Page 30: ...30 C13768 Fig 39 RTU Open System Control Wiring Diagram with Perfect Humidityt 580J 17 30 V ...
Page 49: ...49 48TC 17 30 V 48TC 17 30 V 48TC 17 30 V 580J 17 30 V ...