DIMENSIONAL DRAWING — 559F180,216
LEGEND
KO — Knockout
NOTES:
1. Dimensions in (
) are in millimeters.
2.
Center of gravity.
3.
Direction of airflow.
4. Ductwork to be attached to accessory roof curb or adapter only.
5. For units with electric heat, a field-supplied 90° elbow must be
installed in the supply ductwork below the unit discharge
connection.
6. Minimum clearance:
a. Rear: 7
8
-0
9
(2134) for coil removal. This dimension can be re-
duced to 4
8
-0
9
(1219) if conditions permit coil removal from the
top.
b. Left side: 4
8
-0
9
(1219) for proper condenser coil airflow.
c. Front: 4
8
-0
9
(1219) for control box access.
d. Right side: 4
8
-0
9
(1219) for proper operation of damper and
power exhaust if so equipped.
e. Top: 6
8
-0
9
(1829) to assure proper condenser fan operation.
f. Local codes or jurisdiction may prevail.
7. With the exception of clearance for the condenser coil and the
damper/power exhaust as stated in note no. 6, removable fence or
barricade requires no clearance.
8. Dimensions are from outside of corner post. Allow 0
8
-
5
⁄
16
9
(8) on
each side for top panel drip edge.
UNIT
559F
CORNER WEIGHT*
A
B
C
D
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
180
357
162
348
158
333
151
512
232
216
335
152
470
213
598
271
647
293
*Weights are for unit only and do not include options or crating.
UNIT
559F
DIMENSIONS
X
Y
Z
Ft-in.
mm
Ft-in.
mm
Ft-in.
mm
180
4-10
1219
3-2
965
1-10
559
216
3-10
1168
3-7
1092
1- 8
508
8