AIR DELIVERY — 559F180-300 UNITS (cont)
559F216 (18 TON)
Airflow
(Cfm)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
5400
650
1.24
1095
750
1.54
1366
844
1.84
1646
930
2.14
1942
1011
2.54
2258
5500
658
1.30
1143
757
1.60
1418
850
1.90
1701
935
2.20
2000
1015
2.60
2318
6000
702
1.60
1428
796
1.90
1723
884
2.30
2025
965
2.60
2339
1041
3.00
2669
6500
747
2.00
1757
835
2.30
2073
919
2.70
2394
997
3.10
2725
1070
3.40
3069
7000
792
2.40
2138
877
2.80
2476
957
3.20
2816
1031
3.50
3165
1102
3.90
3525
7200
856
2.60
2311
893
3.00
2657
973
3.40
3006
1045
3.74
3362
1115
4.14
3729
7500
838
2.90
2571
918
3.30
2929
996
3.70
3290
1067
4.10
3658
1135
4.50
4035
8000
885
3.40
3060
962
3.90
3440
1036
4.30
3822
1105
4.70
4209
1170
5.20
4604
8500
932
4.00
3610
1005
4.50
4011
1077
4.90
4414
1143
5.40
4821
—
—
—
9000
980
4.70
4223
1050
5.20
4647
1119
5.70
5071
—
—
—
—
—
—
559F216 (18 TON) (cont)
Airflow
(Cfm)
Standard Belt-Drive Motor
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
5400
1079
2.68
2597
1165
3.32
2954
1238
3.72
3332
1308
4.14
3727
5500
1093
3.00
2658
1168
3.40
3017
1240
3.80
3396
1310
4.20
3793
6000
1115
3.40
3018
1186
3.80
3385
1251
4.20
3771
1322
4.70
4175
6500
1140
3.80
3429
1208
4.30
3805
1274
4.70
4198
1338
5.20
4609
7000
1169
4.40
3898
1233
4.80
4285
1296
5.20
4687
1358
5.70
5106
7200
1181
4.60
4108
1245
5.04
4500
—
—
—
—
—
—
7500
1199
4.90
4422
1262
5.40
4822
—
—
—
—
—
—
8000
1232
5.60
5008
—
—
—
—
—
—
—
—
—
8500
—
—
—
—
—
—
—
—
—
—
—
—
9000
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 2.)
2. Factory-shipped motor drive range is 1047 to 1251 rpm. Other rpms
require a field-supplied drive.
3. Maximum continuous bhp is 5.90 and maximum continuous watts
are 5180. Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
4. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table. See page 47 for
accessory/FIOP static pressure information.
5. Interpolation is permissible. Do not extrapolate.
6. Fan performance is based on wet coils, clean filters, and casing
losses.
7. Extensive motor and drive testing on these units ensures that the full
horsepower range of the motor can be utilized with confidence. Us-
ing your fan motors up to the watts or bhp rating shown will not result
in nuisance tripping or premature motor failure. Unit warranty will not
be affected.
8. Minimum allowable cfm is 300 cfm/ton.
9. Use of a field-supplied motor may affect wire sizing. Contact your lo-
cal representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on
page 62.
44