AIR DELIVERY — 558D036-150 HORIZONTAL DISCHARGE UNITS (cont)
558D048 (4 TON)
Airflow
(Cfm)
Standard Direct-Drive Motor
Low Speed
High Speed
208 v
230, 460, 575 v
208 v
230, 460, 575 v
ESP
Bhp
Watts
ESP
Bhp
Watts
ESP
Bhp
Watts
ESP
Bhp
Watts
1200
0.93
0.41
458
0.97
0.45
506
1.04
0.51
572
1.09
0.56
632
1300
0.86
0.42
471
0.90
0.46
521
0.96
0.52
589
1.02
0.58
651
1400
0.78
0.45
503
0.84
0.49
556
0.90
0.54
616
0.96
0.60
681
1500
0.73
0.47
536
0.76
0.52
593
0.83
0.56
631
0.89
0.62
698
1600
0.67
0.49
557
0.70
0.54
616
0.75
0.58
654
0.82
0.64
723
1700
0.60
0.52
584
0.63
0.57
646
0.67
0.60
678
0.74
0.66
750
1800
0.51
0.54
610
0.54
0.60
674
0.62
0.62
698
0.69
0.68
772
1900
0.40
0.56
629
0.45
0.62
696
0.54
0.64
720
0.62
0.70
796
2000
0.32
0.58
661
0.33
0.65
731
0.47
0.66
744
0.54
0.73
823
LEGEND
Bhp
— Brake Horsepower Input to Fan
ESP
— External Static Pressure (in. wg)
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the
full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in nui-
sance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
3. Use of a field-supplied motor may affect wire sizing. Contact your lo-
cal representative for details.
4. Minimum allowable cfm is 300 cfm/ton.
558D048 (4 TON)
Airflow
(Cfm)
Alternate Direct-Drive Motor
External Static Pressure (in. wg)
0.1
0.2
0.3
0.4
0.6
0.7
0.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1200
514
0.15
158
590
0.20
210
657
0.25
263
723
0.30
315
828 0.42
441
876 0.49
510
924 0.55
578
1300
545
0.18
189
615
0.23
242
680
0.29
305
744
0.35
368
849 0.47
494
895 0.54
562
940 0.60
630
1400
577
0.21
221
642
0.27
284
704
0.33
347
766
0.39
410
870 0.52
546
915 0.59
620
959 0.66
693
1500
609
0.26
273
670
0.31
326
729
0.38
394
788
0.44
462
892 0.58
609
936 0.65
683
980 0.72
757
1600
642
0.30
315
699
0.36
378
755
0.43
447
811
0.49
515
913 0.64
672
957 0.72
751
1001 0.79
830
1700
675
0.36
378
728
0.42
441
782
0.49
510
836
0.55
578
935 0.71
746
979 0.79
825
1023 0.86
904
1800
709
0.41
431
759
0.48
504
810
0.55
578
860
0.62
651
957 0.78
820
1001 0.86
904
1044 0.94
988
1900
743
0.48
504
790
0.55
578
838
0.62
651
886
0.69
725
980 0.86
904
1023 0.95
993
1066 1.03
1082
2000
778
0.55
578
836
0.62
651
875
0.70
730
913
0.77
809
1004 0.94
988
1046 1.03
1082
1088 1.12
1177
558D048 (4 TON) (cont)
Airflow
(Cfm)
Alternate Direct-Drive Motor
External Static Pressure (in. wg)
1.0
1.1
1.2
1.4
1.6
1.8
Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts Rpm Bhp Watts
1200
999 0.66
674 1018 0.67
685 1036 0.68
695 1073 0.71
756 1109 0.75
794 1138 0.79
851
1300
1025 0.74
756 1058 0.79
807 1090 0.84
858 1121 0.87
832 1159 0.90
918 1193 0.95
976
1400
1042 0.81
828 1080 0.88
899
1118 0.95
971 1175 1.06 1014 1206 1.09 1042 1244 1.12 1138
1500
1060 0.88
899 1098 0.96
981 1136 1.04 1063 1205 1.19 1138 1258 1.30 1243 1289 1.34 1282
1600
1080 0.95
971
1117 1.04 1058 1153 1.12 1140 1224 1.29 1234 1287 1.45 1387 1337 1.56 1492
1700
1101 1.03 1053 1137 1.12 1139
1172 1.20 1226 1241 1.38 1320 1307 1.56 1492 1366 1.73 1655
1800
1122 1.11
1134
1157 1.20 1226 1192 1.29 1318 1258 1.48 1415 1323 1.67 1597 1385 1.86 1779
1900
1143 1.21 1237 1179 1.30 1328 1214 1.39 1420 1279 1.58 1511 1341 1.78 1702 1402 1.98 1894
2000
1165 1.31 1339 1200 1.40 1431 1235 1.49 1523 1300 1.69 1616 1361 1.90 1817 1419 2.10 2008
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates a field-supplied drive is required. (See Note 7.)
2.
indicates field-supplied motor and drive are required.
3.
indicates maximum usable bhp/watts.
4. Maximum usable watts input is 1000 and maximum continuous bhp
is 1.00. Extensive motor and electrical testing on these units ensures
that the full range of the motor can be utilized with confidence. Using
your fan motors up to the wattage ratings shown will not result in
nuisance tripping or premature motor failure. Unit warranty will not be
affected. For additional information on motor performance, refer to
Evaporator-Fan Motor Performance table on page 62.
5. Values include losses for filters, unit casing, and wet coils. See
page 47 for accessory/FIOP static pressure information.
6. Use of a field-supplied motor may affect wire sizing. Contact your lo-
cal representative for details.
7. Motor drive range: 835 to 1185 rpm. All other rpms require field-
supplied drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
35