ELECTRIC HEATER CAPACITIES — 558D036-150
UNIT
558D
VOLTAGE
(60 Hz)
ACCESSORY
kW
036
208/230
(single phase)
4.4
6.5
8.7
10.5
13.0*
208/230
(3 phase)
4.4
6.5
8.7
10.5
16.0
460
(3 phase)
6.0
8.8
11.5
14.0
048
208/230
(single phase)
4.4
8.7
13.0*
17.4*
21.0*
208/230
(3 phase)
6.5
8.7
16.0
21.0*
460
(3 phase)
6.0
11.5
14.0*
23.0*
060
208/230
(single phase)
6.5
8.7
13.0*
17.4*
21.0*
208/230
(3 phase)
6.5
10.5
16.0
21.0*
26.5*
460
(3 phase)
6.0
11.5
14.0
23.0*
25.0*
072
208/230
(3 phase)
6.5
10.5
16.0
21.0*
26.5*
460
(3 phase)
6.0
11.5
14.0
23.0*
25.5*
ELECTRIC HEATER CAPACITIES —
558D036-150 (cont)
UNIT
558D
VOLTAGE
(60 Hz)
ACCESSORY
kW
090,102
208/230
(3 phase)
10.4
16.0
24.8
32.0
42.4*
460
(3 phase)
13.9
16.5
27.8
33.0
41.7*
575
(3 phase)
18.0
36.0
120,150
208/230
(3 phase)
10.4
16.0
32.0
42.4*
50.0*
460
(3 phase)
16.5
27.8
33.0
41.7*
50.0*
575
(3 phase)
18.0
36.0
54.0*
*Two heater packages required to provide kW indicated.
NOTES:
1. The kW ratings shown above are at 240, 480, and 575 v. Use the
Electric Heat Multiplication Factors table on page 48 to determine
heater capacity for your particular voltage.
2. Heaters are not available for size 036-072, 575-v units.
ELECTRIC RESISTANCE HEATER DATA — 559F180-300
UNIT
559F
HEATER kW
HEATER
STAGES
% HEAT
PER STAGE
MAXIMUM
STAGES*
Unit Voltages
208
230
460
575
180
26
34
32
—
2
50/50
2
42
56
55
—
2
33/67
3
56
75
80
50
2
50/50
4
216-300
26
34
32
—
2
50/50
2
42
56
55
—
2
33/67
3
56
75
80
—
2
50/50
4
*Maximum number of stages using accessory low-ambient kit or head pressure control device and low-
ambient kit.
NOTE: Heaters are rated at 240 v, 480 v, and 575 v.
64