DIMENSIONAL DRAWING — 558D090-150
UNIT
558D
CORNER WEIGHT*
DIMENSIONS
A
B
C
D
‘‘H’’
‘‘J’’
‘‘K’’
Lb
Kg
Lb
Kg
Lb
Kg
Lb
Kg
Ft-in.
mm
Ft-in.
mm
Ft-in.
mm
090
164
74
140
64
208
94
243
110
1-2
7
⁄
8
378
3-5
5
⁄
16
1050
2-9
11
⁄
16
856
102
165
75
141
64
209
94
245
111
3-3
7
⁄
8
1013
3-5
5
⁄
16
1050
2-9
11
⁄
16
856
120
199
90
170
77
252
114
294
134
2-5
7
⁄
8
759
4-1
5
⁄
16
1253
3-0
3
⁄
8
924
150
202
92
172
78
256
116
300
136
1-2
7
⁄
8
378
4-1
5
⁄
16
1253
3-0
3
⁄
8
924
*Weights are for unit only (aluminum plate fins) and do not include options or crating.
NOTES:
1. Dimensions in [
] are in millimeters.
2.
Center of gravity.
3.
Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces (when not using curb) 0 inches. On horizontal discharge units with
electric heat 1 in. clearance to ductwork for 1 ft.
b. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater clear-
ance is optional.
c. Overhead, 60 in. to assure proper condenser fan operation.
d. Between units, control box side, 42 in. per NEC (National Electrical Code).
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
f. Between unit and block or concrete walls and other grounded surfaces, control box side,
42 in. per NEC.
g. Horizontal supply and return end, 0 inches.
6. With the exception of the clearance for the condenser coil and combustible surfaces as stated in
Notes 5a and b, a removable fence or barricade requires no clearance.
7. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
8. The vertical center of gravity is 1
8
-7
1
⁄
2
9
[495] for 090 and 102, 2
8
-0
9
[610] for 120 and 150 up from the
bottom of the base rail. Horizontal center of gravity is shown.
BOTTOM POWER CHART, THESE HOLES REQ’D FOR USE
WITH ACCESSORY PACKAGES — CRBTMPWR001A00
(
1
⁄
2
(
,
3
⁄
4
(
) OR CRBTMPWR002A00 (
1
⁄
2
(
, 1
1
⁄
4
(
)
THREADED CONDUIT
SIZE
WIRE SIZE
REQ’D HOLE
SIZES (MAX.)
1
⁄
2
(
24 v
7
⁄
8
9
[22.2]
3
⁄
4
(
POWER†
1
1
⁄
8
9
[28.4]
1
1
⁄
4
(
POWER†
1
3
⁄
4
9
[44.4]
†Select either
3
⁄
4
9
or 1
1
⁄
4
9
for power, depending on wire size.
CONNECTION SIZES
A
1
3
⁄
8
9
Diameter [35] Field Power Supply Hole
B
2
1
⁄
2
9
Diameter [64] Power Supply Knockout
C
1
3
⁄
4
9
Diameter [44] Charging Port Hole
D
7
⁄
8
9
Diameter [22] Field Control Wiring Hole
E
3
⁄
4
9
-14 NPT Condensate Drain
F
2
9
Diameter [51] Power Supply Knockout
7