AIR DELIVERY — 559F180-300 UNITS
559F180 (15 TON)
Airflow
(Cfm)
Standard Belt-Drive Motor; 208/230-V and 460-V Units
External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
1.1
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
4500
790
1.02
906
879
1.23
1092
960
1.43
1270
1039
1.64
1456
1114
1.85
1643
1152
1.97
1751
4800
830
1.21
1075
915
1.43
1270
993
1.64
1456
1068
1.86
1652
1140
2.09
1856
1175
2.21
1958
5100
870
1.42
1261
953
1.65
1465
1028
1.88
1670
1099
2.11
1874
1168
2.35
2087
1202
2.47
2194
5400
911
1.66
1474
991
1.90
1687
1063
2.15
1909
1131
2.39
2123
1197
2.64
2345
1230
2.77
2456
5700
952
1.92
1705
1030
2.18
1936
1099
2.44
2167
1165
2.69
2389
1228
2.95
2620
1259
3.09
2740
6000
994
2.21
1963
1069
2.48
2202
1136
2.76
2451
1200
3.03
2691
1260
3.29
2922
1290
3.43
3047
6300
1035
2.53
2247
1109
2.82
2504
1174
3.10
2753
1235
3.39
3011
1294
3.67
3259
1323
3.81
3384
6600
1078
2.88
2558
1148
3.18
2824
1213
3.48
3019
1271
3.78
3357
1329
4.07
3615
1357
4.22
3748
6900
1120
3.26
2895
1188
3.58
3179
1251
3.89
3455
1309
4.20
3730
—
—
—
—
—
—
7200
1163
3.68
3268
1229
4.01
3561
—
—
—
—
—
—
—
—
—
—
—
—
7500
1205
4.13
3668
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
559F180 (15 TON) (cont)
Airflow
(Cfm)
Standard Belt-Drive Motor; 208/230-V and 460-V Units
External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
Rpm
Bhp
Watts
4500
1189
2.09
1856
1264
2.36
2096
1338
2.67
2371
1410
3.00
2664
1479
3.36
2984
4800
1210
2.32
2060
1280
2.58
2291
1351
2.88
2558
1420
3.20
2842
1488
3.55
3153
5100
1235
2.59
2300
1301
2.85
2531
1367
3.13
2780
1433
3.44
3055
1499
3.78
3357
5400
1262
2.89
2567
1325
3.15
2798
1386
3.42
3037
1449
3.72
3304
1512
4.05
3597
5700
1290
3.22
2860
1351
3.48
3091
1410
3.76
3339
1468
4.05
3597
—
—
—
6000
1320
3.57
3171
1379
3.85
3419
1436
4.13
3668
—
—
—
—
—
—
6300
1351
3.95
3508
1408
4.24
3766
—
—
—
—
—
—
—
—
—
6600
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
6900
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7200
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
7500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
LEGEND
Bhp
— Brake Horsepower Input to Fan
FIOP
— Factory-Installed Option
Watts — Input Watts to Motor
NOTES:
1. Boldface indicates field-supplied drive is required. (See Note 2.)
2. Factory-shipped motor drive range is 1227 to 1559 rpm. Other rpms
require a field-supplied drive.
3. Maximum continuous bhp is 4.25 and maximum continuous watts
are 3775. Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.
4. Static pressure losses (i.e., economizer) must be added to external
static pressure before entering Air Delivery table. See page 47 for
accessory/FIOP static pressure information.
5. Interpolation is permissible. Do not extrapolate.
6. Fan performance is based on wet coils, clean filters, and casing
losses.
7. Extensive motor and drive testing on these units ensures that the full
horsepower and watts range of the motor can be utilized with confi-
dence. Using your fan motors up to the watts or bhp rating shown will
not result in nuisance tripping or premature motor failure. Unit war-
ranty will not be affected.
8. Minimum allowable cfm is 300 cfm/ton.
9. Use of a field-supplied motor may affect wire sizing. Contact your lo-
cal representative for details. For additional information on motor
performance, refer to Evaporator-Fan Motor Performance table on
page 62.
42