background image

IV. INDOOR FAN SERVICE AND REPLACEMENT

A. 542J150 Units (Fig. 28)

NOTE:

To remove belts only, follow Steps 1-6.

1. Remove filter and supply-air section panels.

2. Remove unit top cover.

3. Loosen carriage nuts A and B holding motor mount as-

sembly to fan scroll side plates.

4. Loosen screw C.

5. Rotate motor mount assembly (with motor attached)

as far as possible away from indoor coil.

6. Remove belt.

7. Rotate motor mount assembly back past original posi-

tion toward indoor coil.

8. Remove motor mounting nuts D and E (both sides).

9. Lift motor up through top of unit.

10. Reverse Steps 1-9 to reinstall motor.

11. Check and adjust belt tension as necessary.

B. 542J180 Units (See Fig. 29)

The 180 units use a fan motor mounting system that fea-
tures a slide-out motor mounting plate. To replace or service
the motor, slide out the bracket.

1. Remove the indoor-fan access panel and the heating

control access panel.

2. Remove the center post (located between the indoor fan

and heating control access panels) and all screws se-
curing it.

3. Loosen nuts on the 2 carriage bolts in the motor mount-

ing base.

4. Using jacking bolt under motor base, raise motor to top

of slide and remove belt. Secure motor in this position
by tightening the nuts on the carriage bolts.

5. Remove the belt drive.

6. Remove jacking bolt and tapped jacking bolt plate.

7. Remove the 2 screws that secure the motor mounting

plate to the motor support channel.

8. Remove the 3 screws from the end of the motor sup-

port channel that interfere with the motor slide path.

9. Slide out the motor and motor mounting plate.

10. Disconnect wiring connections and remove the 4 mount-

ing bolts.

11. Remove the motor.

12. To install the new motor, reverse Steps 1-11.

13. Check and adjust belt tension as necessary.

V. ECONOMIZER ADJUSTMENT

See Tables 11 and 12 for checkout and enthalpy simulation.
Make certain the outdoor-air damper is fully closed and the
return-air damper is fully open before completing the follow-
ing steps:

1. Turn on power to the unit.

2. Turn the thermostat fan switch to the ON position. The

damper will go to the vent position.

3. Adjust the vent position with the minimum position

adjustment on the economizer motor control module.
See Fig. 17.

4. Set the system selector switch to COOL position and

set the cooling temperature selector to its lowest
setting.

Table 11 — Economizer Checkout Procedures

TEST PROCEDURE

RESULTS

A. Disconnect power at

TR and TR1.
Disconnect jumper
between P and
P1. See Fig. 17.

B. Jumper TR to 1.
C. Jumper T1 to T.
D. Disconnect outdoor-air

thermostat connections
from S

O

and +.

Factory-installed
800 ohm resistor
should remain connected
to S

R

and +.

E. Reconnect power to

terminals TR and TR1.

1. LED (light-emitting diode)

should be off.

2. Motor is in closed position.

TEST PROCEDURE

RESULTS

Disconnect factory-installed
resistor from terminals
S

R

and +.

1 LED (light-emitting diode)

should be on.

2. Motor drives toward open.

Table 12 — High and Low Outdoor-Air Simulation

TEST PROCEDURE

RESULTS

A. Reconnect factory-installed

800 ohm resistor
between terminals
S

R

and +.

B. Connect 1200 ohm

checkout resistor between
terminals S

O

and +.

C. Turn set point potentiometer

to position A.

Low outdoor air temperature
test results:
1. LED (light-emitting diode)

should be on.

2. Motor drives toward open.

D. Turn set point potentiometer

to position D.

E. Disconnect 1200 ohm

checkout resistor.

High outdoor air temperature
test results:
1. LED should be off.
2. Motor drives toward closed.

NOTE:

The cooling mode may also be simulated by remov-

ing the thermostat wires from terminals Y1 and Y2 and in-
stalling a jumper between terminals R and Y1. Refer to unit
label diagram for terminal locations.

5. Set the outdoor-air thermostat (OAT), located in the

economizer section of the unit to 75 F.

6. If the outdoor temperature is below 75 F, the econo-

mizer will control the leaving air with the mixed-air
sensor. If the outdoor air is above 75 F, place a jumper
around the contacts of the OAT.

7. Jumper terminal T to terminal T1 on the module (see

Fig. 17). The economizer will go to the full open posi-
tion. The outdoor-air damper will go to the full open
position, and the return-air damper will go to the full
closed position.

8. Adjust mechanical linkage, if necessary, for correct po-

sitioning. It may be necessary to remove the filters to
adjust the linkage.

—22—

Summary of Contents for 542J Series

Page 1: ...e WARNING Before performing service or mainte nance operations on unit turn off main power switch to unit Electrical shock could cause personal injury 1 The power supply volts hertz and phase must cor...

Page 2: ...9 1219 for proper outdoor coil airflow Front 48 09 1219 for control box access Right side 48 09 1219 for proper operation of damper and power ex haust if so equipped Top 68 09 1829 to assure proper ou...

Page 3: ...ont 48 09 1219 for control box access Right side 48 09 1219 for proper operation of damper and power ex haust if so equipped Top 68 09 1829 to assure proper outdoor fan operation Local codes or jurisd...

Page 4: ...n Duct work must be attached to curb Electric and control power can be routed through the curb or control box end panel see Fig 2 and 3 IMPORTANT The gasketing of the unit to the roof curb is critical...

Page 5: ...68 29 1880 08 61 49 159 18 25 89 371 LEGEND COMP SECT Compressor Section NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 1 2 in thick neoprene coated 2 lb density 3 Dimensions i...

Page 6: ...ging instructions on unit IMPORTANT Be sure to remove skids from under unit be fore setting unit in place A properly positioned unit will have the following clearances between unit and roof curb 1 4 i...

Page 7: ...Ball Maximum Allowable Rpm 1550 1550 Motor Pulley Pitch Diameter Min Max in 3 1 4 1 3 7 4 7 Nomimal Motor Shaft Diameter in 13 16 17 16 Fan Pulley Pitch Diameter in 6 0 11 4 Belt Quantity Type Length...

Page 8: ...com partment or conduit approved for electrical ground when installed in accordance with the NEC ANSI American National Standards Institute NFPA 70 in Canada Canadian Electrical Code CSA Canadian Stan...

Page 9: ...efore making any wiring changes Electrical shock can cause personal injury or death For operation on 208 v 1 Remove the cap from the splice containing the orange 230 v transformer primary lead and 2 b...

Page 10: ...Overcurrent Protection NEC National Electrical Code RLA Rated Load Amps Heater capacity kW is based on heater voltage of 208 v 240 v and 480 v If power distribution voltage to unit varies from rated h...

Page 11: ...d 2 Set system selector switch at OFF position 3 Turn damper adjustment knob located on economizer mo tor control module clockwise slowly until dampers as sume desired position Do not manually operate...

Page 12: ...ide panels located on the sides of the outdoor air inlet opening 5 Match notches in hood top panel to unit top panel screws Insert hood flange between top panel flange and unit Tighten screws 6 Hold h...

Page 13: ...are completed and tight d Inspect coil fins If damaged during shipping and han dling carefully straighten fins with a fin comb 4 Verify the following conditions a Make sure that outdoor fan blades are...

Page 14: ...atically changes from heating operation to cooling operation when the temperature of the conditioned space rises to the cooling lever setting When the temperature of the con ditioned space falls to th...

Page 15: ...and of the thermostat to satisfy the occu pied space demands Units With Economizer Upon a call for cooling when outdoor ambient temperature is above the temperature control setting the indoor and out...

Page 16: ...1247 2036 2 32 1317 2268 2 58 1384 2503 2 85 1448 2742 3 12 1510 2983 3 40 4750 1269 2232 2 54 1337 2468 2 81 1403 2707 3 08 1465 2948 3 36 1526 3194 3 64 5000 1291 2441 2 78 1358 2680 3 05 1422 2923...

Page 17: ...660 4 1 1271 4052 4 5 1336 4461 5 0 1399 4887 5 5 6400 1151 3549 4 0 1218 3928 4 4 1283 4325 4 8 1347 4739 5 3 1409 5169 5 8 6900 1167 3821 4 3 1232 4207 4 7 1295 4608 5 2 1357 5026 5 6 1417 5460 6 1...

Page 18: ...at this cfm is above unit maximum cfm limit NOTES 1 Heaters are rated at 208 240 v and 480 v 2 The factory assembled horizontal adapter substantially improves fan performance See Fig 23 3 The static p...

Page 19: ...r or two position damper control The damper motor will be energized at terminal TR and the damper will drive open to minimum vent position The damper motor will stop and the damper will remain in the...

Page 20: ...at least twice during each heating and cooling season and when ever the filters become clogged with dust and lint Replace filters with the same dimensional size and type as originally provided when ne...

Page 21: ...see Fig 25 4 Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed Increas ing fan speed increases load on motor Do not exceed maxi mum speed specifie...

Page 22: ...damper will go to the vent position 3 Adjust the vent position with the minimum position adjustment on the economizer motor control module See Fig 17 4 Set the system selector switch to COOL position...

Page 23: ...age and temperature sensing device are required Connect temperature sensing device to service port on suction line and insulate it so that outdoor ambient temperature does not af fect reading Indoor a...

Page 24: ...ts frost build up and turns off the compressor allowing the coil to clear Once the frost has melted the compressor can be reenergized X RELIEF DEVICES All units have relief devices to protect against...

Page 25: ...k valve 4 The refrigerant then flows through the 4 way valve accumulator and back to the compressor NOTES 1 Hot gas from compressor flows through the 4 way valve and is directed to the indoor coil hea...

Page 26: ...nt short cycling on com pressor overload and safety devices Before replacing CLO check these devices 9 Remove jumper between terminals RC an RH 1 AHA Adjustable Heat Anticipator BRK W AT Breaks With A...

Page 27: ...Fig 33 Typical Label Diagram Schematic 542J180 208 230 V 60 Hz Unit Shown ELECTRIC HEAT AHA SETTING 208 240 V Amps 208 240 V kW 1st 2nd A 72 82 25 7 34 2 1 00 0 52 B 117 135 42 3 56 1 1 00 0 78 27...

Page 28: ...Fig 33 Typical Label Diagram Schematic 542J180 208 230 V 60 Hz Unit Shown cont 28...

Page 29: ...TROUBLESHOOTING CHART HEATING CYCLE ODT Outdoor Temperature 29...

Page 30: ...TROUBLESHOOTING CHART COOLING CYCLE Copyright 1997 Carrier Corporation CATALOG NO BDP 3354 237...

Page 31: ......

Page 32: ...G ORIFICE AND VERIFY SET SCREW IS TIGHT M VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED START UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 COMPRESSOR AMPS COMPRESSOR NO 1 L1 L...

Reviews: