Table 1 — Specifications
UNIT SIZE 542J
150
180
OPERATING WT (lb)
Unit
1615
1925
Economizer
110
110
Roof Curb*
200
200
COMPRESSOR
Semi-Hermetic
Type (Quantity)
060-328 (1)
060-818 (2)
No. Cylinders
6
4
Oil Charge (oz.) (Cool Circuit)
115
88
REFRIGERANT TYPE
R-22
Charge (lb)
System 1
26.0
16.5
System 2
—
16.5
OUTDOOR COIL
3
⁄
8
in., Internally-Grooved Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in.
3...15
3...15
Total Face Area (sq ft)
21.7
21.7
OUTDOOR FAN
Propeller Type, Direct Drive
Nominal Cfm
9,000
Number...Diameter (in.)
3...22
Motor Hp...Rpm
1
⁄
2
...1075
Watts Input (Total)
1090
INDOOR COIL
3
⁄
8
in., Internally-Grooved Copper Tubes, Aluminum or Copper Lanced Fins, Acutrol™ Feed Device
Expansion Device
Fixed Orifice
Rows...Fins/in.
3...15
3...15
Total Face Area (sq ft)
17.5
17.5
INDOOR FAN
Centrifugal Type
Quantity...Size (in.)
2...10 x 10
2...12 x 12
Type Drive
Belt
Belt
Nominal Cfm
5000
6000
Motor Hp
3.7
5.0
Maximum Continuous Bhp
4.25
5.90
Motor Frame Size
56H
184T
Fan Rpm Range
862-1132
799-1010
Motor Bearing Type
Ball
Ball
Maximum Allowable Rpm
1550
1550
Motor Pulley Pitch Diameter
Min/Max (in.)
3.1/4.1
3.7/4.7
Nomimal Motor Shaft Diameter (in.)
1
3
⁄
16
1
7
⁄
16
Fan Pulley Pitch Diameter (in.)
6.0
11.4
Belt, Quantity...Type...Length (in.)
1...BX...42
1...BX...46
Pulley Center Line Distance (in.)
13.5-15.5
13.3-14.8
Speed Change per Full Turn of
Movable Pulley Flange (rpm)
54
42
Movable Puley Maximum Full Turns
from Closed Position
6†
6†
Factory Setting
3
3
Factory Speed Setting (Rpm)
1024
926
Motor Efficiency
0.84
0.84
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
—
Cutout
426
Reset (Auto.)
320
LOW-PRESSURE SWITCH (psig)
Cutout
7
Reset (Auto.)
22
FREEZE PROTECTION THERMOSTAT (F)
Opens
30 ± 5
Closes
45 ± 5
OUTDOOR AIR INLET SCREENS
Cleanable
Quantity...Size (in.)
2...20 x 25 x 1
1...20 x 20 x 1
RETURN-AIR FILTERS
10% Efficient — 2-in. Throwaway Fiberglass
Quantity... Size (in.)
4...20 x 20 x 2
4...16 x 20 x 2
DEFROST THERMOSTAT
Defrost Timer
30 Min (Adjustable to 50 or 90 Min)
Closes (F)
28
Opens (F)
65
LEGEND
Al
— Aluminum
Bhp
— Brake Horsepower
Cu
— Copper
FIOP — Factory-Installed Option
*Weight of 14 in. roof curb.
†Cannot be set to 0 or
1
⁄
2
turns open.
NOTE: The 542J units have a low-pressure/loss-of-charge switch (stand-
ard) located on the suction side.
—7—
Summary of Contents for 542J Series
Page 28: ...Fig 33 Typical Label Diagram Schematic 542J180 208 230 V 60 Hz Unit Shown cont 28...
Page 29: ...TROUBLESHOOTING CHART HEATING CYCLE ODT Outdoor Temperature 29...
Page 30: ...TROUBLESHOOTING CHART COOLING CYCLE Copyright 1997 Carrier Corporation CATALOG NO BDP 3354 237...
Page 31: ......