Table 9 — Fan Rpm at Motor Pulley Settings* (Factory-Supplied Drives)
UNIT
542J
MOTOR PULLEY TURNS OPEN
0
1
⁄
2
1
1
1
⁄
2
2
2
1
⁄
2
3
3
1
⁄
2
4
4
1
⁄
2
5
5
1
⁄
2
6
150
†
†
1132
1105
1078
1051
1024
997
970
943
916
889
862
180
†
†
1010
989
968
947
926
905
883
862
841
820
799
*Approximate fan rpm shown.
†Due to belt and pulley size, pulley cannot be set to this number of turns
open.
NOTE: To run units at speeds not listed, field-supplied drives are
required.
C. Outdoor-Fan Adjustment (Fig. 26)
1. Turn off unit power supply.
2. Remove access panel(s) closest to the fan to be adjusted.
3. Loosen fan hub setscrews.
4. Adjust fan height on shaft using a straightedge placed
across the fan orifice.
5. Tighten setscrews and replace panel(s).
6. Turn on unit power.
D. Ventilation Sequence
If unit is equipped with economizer or two-position damper,
the damper will open to the minimum position whenever the
indoor fan runs.
Two-Position Damper
Whenever the indoor fan is energized (during heating, cool-
ing, or continuous fan), 24-v power is on indoor fan contactor
(IFC) and the economizer or two-position damper control. The
damper motor will be energized at terminal TR, and the damper
will drive open to minimum vent position. The damper motor
will stop, and the damper will remain in the minimum ven-
tilation position until the indoor fan is shut off. When the in-
door fan is shut off, the damper motor will spring return to
the closed position.
Economizer
When unit is equipped with an economizer, additional out-
door air can be brought in through the damper to provide cool-
ing. If the unit calls for cooling and the outdoor-air tempera-
ture is below the outdoor-air thermostat setting, the economizer
motor starts. The damper drives open until it reaches full open
or until the mixed-air set point is met. When cooling load is
satisfied, or outdoor air is no longer below the outdoor-air ther-
mostat setting, the damper returns to the minimum position
if indoor fan is running, or closes if the indoor fan is not
running.
If the leaving-air thermistor (located on the indoor-fan blower
housing) senses a leaving-air temperature less than 50 F, the
damper closes until the leaving-air temperature is above
50 F.
Fig. 25 — Indoor-Fan Pulley Alignment
and Adjustment
NOTE: Dimensions are in inches.
Fig. 26 — Outdoor Fan Adjustment
—19—