Table 6 — Air Delivery, 542J180 Units

AIRFLOW

(Cfm)

STANDARD BELT-DRIVE MOTOR

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

4500

584

717

0.8

695

952

1.1

798

1205

1.3

893

1483

1.7

984

1786

2.0

4800

609

839

0.9

717

1085

1.2

815

1346

1.5

907

1630

1.8

994

1938

2.2

5100

634

971

1.1

738

1229

1.4

833

1500

1.7

921

1791

2.0

1006

2104

2.4

5400

660

1118

1.3

760

1389

1.6

852

1669

1.9

937

1968

2.2

1019

2286

2.6

5700

687

1284

1.4

783

1566

1.8

873

1858

2.1

956

2165

2.4

1034

2490

2.8

6000

712

1458

1.6

805

1752

2.0

892

2055

2.3

973

2371

2.7

1049

2703

3.0

6300

736

1644

1.8

826

1952

2.2

911

2265

2.5

990

2591

2.9

1064

2930

3.3

6600

763

1856

2.1

851

2176

2.4

933

2502

2.8

1010

2837

3.2

1082

3186

3.6

6900

788

2078

2.3

873

2410

2.7

954

2747

3.1

1029

3093

3.5

1099

3451

3.9

7200

813

2316

2.6

896

2662

3.0

975

3011

3.4

1048

3367

3.8

1117

3734

4.2

7500

841

2584

2.9

921

2943

3.3

998

3304

3.7

1070

3672

4.1

1137

4049

4.5

Table 6 — Air Delivery, 542J180 Units (cont)

AIRFLOW

(Cfm)

STANDARD BELT-DRIVE MOTOR

External Static Pressure (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

Rpm

Watts

Bhp

4500

1070

2113

2.4

1151

2458

2.8

1229

2819

3.2

1302

3194

3.6

1371

3578

4.0

4800

1078

2269

2.5

1157

2620

2.9

1233

2990

3.3

1306

3374

3.8

1375

3769

4.2

5100

1086

2439

2.7

1164

2795

3.1

1238

3170

3.5

1310

3560

4.0

1378

3965

4.4

5400

1097

2626

2.9

1172

2986

3.3

1245

3366

3.8

1315

3763

4.2

1382

4174

4.7

5700

1110

2835

3.2

1183

3200

3.6

1253

3584

4.0

1322

3986

4.5

1388

4404

4.9

6000

1122

3053

3.4

1193

3422

3.8

1262

3810

4.3

1329

4216

4.7

1393

4638

5.2

6300

1135

3286

3.7

1204

3660

4.1

1271

4052

4.5

1336

4461

5.0

1399

4887

5.5

6400

1151

3549

4.0

1218

3928

4.4

1283

4325

4.8

1347

4739

5.3

1409

5169

5.8

6900

1167

3821

4.3

1232

4207

4.7

1295

4608

5.2

1357

5026

5.6

1417

5460

6.1

7200

1183

4113

4.6

1246

4505

5.0

1308

4912

5.5

1368

5335

6.0

1427

5773

6.5

7500

1202

4437

5.0

1264

4837

5.4

1324

5251

5.9

1383

5679

6.4

1440

6122

6.9

LEGEND

Bhp

— Brake Horsepower Input to Fan

FIOP

— Factory-Installed Option

Watts — Input Watts to Motor

NOTES:
1. Boldface indicates field-supplied drive required.

2.

indicates field-supplied motor and drive required.

3.

indicates maximum bhp/watts of standard motor and drive.

4. Factory-shipped motor drive range is 799 to 1010 rpm. Other rpms

may require a field-supplied drive.

5. Maximum continuous bhp is 5.90 and maximum continuous watts

are 5180. Do not adjust motor rpm such that motor maximum bhp
and/or watts is exceeded at the maximum operating cfm.

6. Static pressure losses (i.e., economizer) must be added to external

static pressure before entering Air Delivery table.

7. Interpolation is permissible. Do not extrapolate.
8. Fan performance is based on wet coils, clean filters, and casing losses.

See Table 7 for accessory/FIOP static pressure information.

9. Extensive motor and drive testing on these units ensures that the full

horsepower and watts range of the motor can be utilized with confi-
dence. Using your fan motors up to the watts or bhp rating shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.

NOTE: The 389210-201 high static regain adapter accessory may be
used to provide horizontal supply/return.

Fig. 23 — Horizontal Supply/Return Fan Performance with 389210-201 High Static Regain Adapter

NOTE: The 389210-201 horizontal supply/return adapter accessory im-
proves 542J fan performance by increasing external static pressure by
amount shown above.

—17—

Summary of Contents for 542J Series

Page 1: ...e WARNING Before performing service or mainte nance operations on unit turn off main power switch to unit Electrical shock could cause personal injury 1 The power supply volts hertz and phase must cor...

Page 2: ...9 1219 for proper outdoor coil airflow Front 48 09 1219 for control box access Right side 48 09 1219 for proper operation of damper and power ex haust if so equipped Top 68 09 1829 to assure proper ou...

Page 3: ...ont 48 09 1219 for control box access Right side 48 09 1219 for proper operation of damper and power ex haust if so equipped Top 68 09 1829 to assure proper outdoor fan operation Local codes or jurisd...

Page 4: ...n Duct work must be attached to curb Electric and control power can be routed through the curb or control box end panel see Fig 2 and 3 IMPORTANT The gasketing of the unit to the roof curb is critical...

Page 5: ...68 29 1880 08 61 49 159 18 25 89 371 LEGEND COMP SECT Compressor Section NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 1 2 in thick neoprene coated 2 lb density 3 Dimensions i...

Page 6: ...ging instructions on unit IMPORTANT Be sure to remove skids from under unit be fore setting unit in place A properly positioned unit will have the following clearances between unit and roof curb 1 4 i...

Page 7: ...Ball Maximum Allowable Rpm 1550 1550 Motor Pulley Pitch Diameter Min Max in 3 1 4 1 3 7 4 7 Nomimal Motor Shaft Diameter in 13 16 17 16 Fan Pulley Pitch Diameter in 6 0 11 4 Belt Quantity Type Length...

Page 8: ...com partment or conduit approved for electrical ground when installed in accordance with the NEC ANSI American National Standards Institute NFPA 70 in Canada Canadian Electrical Code CSA Canadian Stan...

Page 9: ...efore making any wiring changes Electrical shock can cause personal injury or death For operation on 208 v 1 Remove the cap from the splice containing the orange 230 v transformer primary lead and 2 b...

Page 10: ...Overcurrent Protection NEC National Electrical Code RLA Rated Load Amps Heater capacity kW is based on heater voltage of 208 v 240 v and 480 v If power distribution voltage to unit varies from rated h...

Page 11: ...d 2 Set system selector switch at OFF position 3 Turn damper adjustment knob located on economizer mo tor control module clockwise slowly until dampers as sume desired position Do not manually operate...

Page 12: ...ide panels located on the sides of the outdoor air inlet opening 5 Match notches in hood top panel to unit top panel screws Insert hood flange between top panel flange and unit Tighten screws 6 Hold h...

Page 13: ...are completed and tight d Inspect coil fins If damaged during shipping and han dling carefully straighten fins with a fin comb 4 Verify the following conditions a Make sure that outdoor fan blades are...

Page 14: ...atically changes from heating operation to cooling operation when the temperature of the conditioned space rises to the cooling lever setting When the temperature of the con ditioned space falls to th...

Page 15: ...and of the thermostat to satisfy the occu pied space demands Units With Economizer Upon a call for cooling when outdoor ambient temperature is above the temperature control setting the indoor and out...

Page 16: ...1247 2036 2 32 1317 2268 2 58 1384 2503 2 85 1448 2742 3 12 1510 2983 3 40 4750 1269 2232 2 54 1337 2468 2 81 1403 2707 3 08 1465 2948 3 36 1526 3194 3 64 5000 1291 2441 2 78 1358 2680 3 05 1422 2923...

Page 17: ...660 4 1 1271 4052 4 5 1336 4461 5 0 1399 4887 5 5 6400 1151 3549 4 0 1218 3928 4 4 1283 4325 4 8 1347 4739 5 3 1409 5169 5 8 6900 1167 3821 4 3 1232 4207 4 7 1295 4608 5 2 1357 5026 5 6 1417 5460 6 1...

Page 18: ...at this cfm is above unit maximum cfm limit NOTES 1 Heaters are rated at 208 240 v and 480 v 2 The factory assembled horizontal adapter substantially improves fan performance See Fig 23 3 The static p...

Page 19: ...r or two position damper control The damper motor will be energized at terminal TR and the damper will drive open to minimum vent position The damper motor will stop and the damper will remain in the...

Page 20: ...at least twice during each heating and cooling season and when ever the filters become clogged with dust and lint Replace filters with the same dimensional size and type as originally provided when ne...

Page 21: ...see Fig 25 4 Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed Increas ing fan speed increases load on motor Do not exceed maxi mum speed specifie...

Page 22: ...damper will go to the vent position 3 Adjust the vent position with the minimum position adjustment on the economizer motor control module See Fig 17 4 Set the system selector switch to COOL position...

Page 23: ...age and temperature sensing device are required Connect temperature sensing device to service port on suction line and insulate it so that outdoor ambient temperature does not af fect reading Indoor a...

Page 24: ...ts frost build up and turns off the compressor allowing the coil to clear Once the frost has melted the compressor can be reenergized X RELIEF DEVICES All units have relief devices to protect against...

Page 25: ...k valve 4 The refrigerant then flows through the 4 way valve accumulator and back to the compressor NOTES 1 Hot gas from compressor flows through the 4 way valve and is directed to the indoor coil hea...

Page 26: ...nt short cycling on com pressor overload and safety devices Before replacing CLO check these devices 9 Remove jumper between terminals RC an RH 1 AHA Adjustable Heat Anticipator BRK W AT Breaks With A...

Page 27: ...Fig 33 Typical Label Diagram Schematic 542J180 208 230 V 60 Hz Unit Shown ELECTRIC HEAT AHA SETTING 208 240 V Amps 208 240 V kW 1st 2nd A 72 82 25 7 34 2 1 00 0 52 B 117 135 42 3 56 1 1 00 0 78 27...

Page 28: ...Fig 33 Typical Label Diagram Schematic 542J180 208 230 V 60 Hz Unit Shown cont 28...

Page 29: ...TROUBLESHOOTING CHART HEATING CYCLE ODT Outdoor Temperature 29...

Page 30: ...TROUBLESHOOTING CHART COOLING CYCLE Copyright 1997 Carrier Corporation CATALOG NO BDP 3354 237...

Page 31: ......

Page 32: ...G ORIFICE AND VERIFY SET SCREW IS TIGHT M VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED START UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 COMPRESSOR AMPS COMPRESSOR NO 1 L1 L...

Reviews: