background image

CARE AND MAINTENANCE

To ensure continuing high performance, and to minimize the
possibility of premature equipment failure, periodic mainte-
nance must be performed on this equipment. This combina-
tion heating/cooling unit should be inspected at least once each
year by a qualified service person.

NOTE TO EQUIPMENT OWNER:

Consult your local dealer

about the availability of a maintenance contract.

WARNING:

The ability to properly perform mainte-

nance on this equipment requires certain expertise,
mechanical skills, tools, and equipment. If you do not
possess these, do not attempt to perform any mainte-
nance on this equipment other than those procedures
recommended in the User’s Manual. FAILURE TO HEED
THIS WARNING COULD RESULT IN SERIOUS PER-
SONAL INJURY AND POSSIBLE DAMAGE TO THIS
EQUIPMENT.

The minimum maintenance requirements for this equipment
are as follows:

1. Inspect air filters each month. Clean or replace when

necessary.

2. Inspect cooling coil, drain pan, and condensate drain each

cooling season for cleanliness. Clean when necessary.

3. Inspect blower motor and wheel each heating and

cooling season. Clean and lubricate (if required) when
necessary.

4. Check electrical connections for tightness and controls

for proper operation each heating and cooling season.
Service when necessary.

5. Check and inspect heating section before each heating

season.

6. Check and clean vent screen if needed.

WARNING:

Failure to follow these warnings could re-

sult in serious personal injury:
1. Turn off electrical power to the unit before perform-

ing any maintenance or service on the unit.

2. Use extreme caution when removing panels and parts.

As with any mechanical equipment, personal injury
can result from sharp edges, etc.

3. Never place anything combustible either on, or in con-

tact with, the unit.

4. Should overheating occur, shut off the electrical

supply.

I. AIR FILTER

CAUTION:

Never operate the unit without a suit-

able air filter in the return-air duct system. Always re-
place the filter with the same dimensional size and type
as originally installed. See Table 1 for recommended fil-
ter sizes.

Inspect air filters at least once each month and replace at
least twice during each heating and cooling season and when-
ever the filters become clogged with dust and lint.

Replace filters with the same dimensional size and type as
originally provided when necessary.

SERVICE

WARNING:

Before beginning any maintenance, be

sure to turn off power at the main disconnect switch.
TAG THE SWITCH WITH A SUITABLE WARNING
LABEL.

I. CLEANING

Inspect unit interior at the beginning of each heating and cool-
ing season or as operating conditions require. Remove unit
top cover and/or side panels for access to unit interior.

A. Indoor Coil

Clean coil using a commercial coil cleaner or dishwasher de-
tergent in a pressurized spray canister. Wash both sides of
coil and flush with clean water.

B. Outdoor Coil

Clean outdoor coil annually and as required by location and
outdoor-air conditions. Inspect coil monthly and clean as
required.

C. Condensate DraIns

Check and clean each year at start of cooling season.

D. Filters

Clean or replace at start of each heating and cooling sea-
son or more often if operating conditions require. Refer to
Table 1 for type and size.

E. Outdoor-Air Inlet Screens

Clean screens with steam or hot water and a mild detergent.
Do not substitute throwaway filters for screens.

II. LUBRICATION

A. Compressors

Each compressor is charged with the correct amount of oil at
the factory. Observe the level in the sight glass immediately
after shutdown while the oil is still warm. If the oil level is
observed when the oil is cold, the level observed may be a
mixture of oil and refrigerant which is not a true indication
of the oil level. If oil level observed is not between the low
limit and high limit levels as indicated in Fig. 27, add oil un-
til it is in the correct range.

If oil charge is above sight glass, do not remove any oil until
the compressor crankcase heater has been energized for at
least 24 hours.

B. Fan Shaft Bearings

For 150 units, the bearings are permanently lubricated. No
field lubrication is required. For 180 units, lubricate bear-
ings at least every 6 months with suitable bearing grease.
Extended grease line is provided for far side fan bearing
(opposite drive side). Typical lubricants are given below:

MANUFACTURER

LUBRICANT

Texaco

Regal AFB-2*

Mobil

Mobilplex EP No. 1

Sunoco

Prestige 42

Texaco

Multifak 2

*Preferred lubricant because it contains rust and oxidation inhibitors.

—20—

Summary of Contents for 542J Series

Page 1: ...e WARNING Before performing service or mainte nance operations on unit turn off main power switch to unit Electrical shock could cause personal injury 1 The power supply volts hertz and phase must cor...

Page 2: ...9 1219 for proper outdoor coil airflow Front 48 09 1219 for control box access Right side 48 09 1219 for proper operation of damper and power ex haust if so equipped Top 68 09 1829 to assure proper ou...

Page 3: ...ont 48 09 1219 for control box access Right side 48 09 1219 for proper operation of damper and power ex haust if so equipped Top 68 09 1829 to assure proper outdoor fan operation Local codes or jurisd...

Page 4: ...n Duct work must be attached to curb Electric and control power can be routed through the curb or control box end panel see Fig 2 and 3 IMPORTANT The gasketing of the unit to the roof curb is critical...

Page 5: ...68 29 1880 08 61 49 159 18 25 89 371 LEGEND COMP SECT Compressor Section NOTES 1 Roof curb accessory is shipped unassembled 2 Insulated panels 1 2 in thick neoprene coated 2 lb density 3 Dimensions i...

Page 6: ...ging instructions on unit IMPORTANT Be sure to remove skids from under unit be fore setting unit in place A properly positioned unit will have the following clearances between unit and roof curb 1 4 i...

Page 7: ...Ball Maximum Allowable Rpm 1550 1550 Motor Pulley Pitch Diameter Min Max in 3 1 4 1 3 7 4 7 Nomimal Motor Shaft Diameter in 13 16 17 16 Fan Pulley Pitch Diameter in 6 0 11 4 Belt Quantity Type Length...

Page 8: ...com partment or conduit approved for electrical ground when installed in accordance with the NEC ANSI American National Standards Institute NFPA 70 in Canada Canadian Electrical Code CSA Canadian Stan...

Page 9: ...efore making any wiring changes Electrical shock can cause personal injury or death For operation on 208 v 1 Remove the cap from the splice containing the orange 230 v transformer primary lead and 2 b...

Page 10: ...Overcurrent Protection NEC National Electrical Code RLA Rated Load Amps Heater capacity kW is based on heater voltage of 208 v 240 v and 480 v If power distribution voltage to unit varies from rated h...

Page 11: ...d 2 Set system selector switch at OFF position 3 Turn damper adjustment knob located on economizer mo tor control module clockwise slowly until dampers as sume desired position Do not manually operate...

Page 12: ...ide panels located on the sides of the outdoor air inlet opening 5 Match notches in hood top panel to unit top panel screws Insert hood flange between top panel flange and unit Tighten screws 6 Hold h...

Page 13: ...are completed and tight d Inspect coil fins If damaged during shipping and han dling carefully straighten fins with a fin comb 4 Verify the following conditions a Make sure that outdoor fan blades are...

Page 14: ...atically changes from heating operation to cooling operation when the temperature of the conditioned space rises to the cooling lever setting When the temperature of the con ditioned space falls to th...

Page 15: ...and of the thermostat to satisfy the occu pied space demands Units With Economizer Upon a call for cooling when outdoor ambient temperature is above the temperature control setting the indoor and out...

Page 16: ...1247 2036 2 32 1317 2268 2 58 1384 2503 2 85 1448 2742 3 12 1510 2983 3 40 4750 1269 2232 2 54 1337 2468 2 81 1403 2707 3 08 1465 2948 3 36 1526 3194 3 64 5000 1291 2441 2 78 1358 2680 3 05 1422 2923...

Page 17: ...660 4 1 1271 4052 4 5 1336 4461 5 0 1399 4887 5 5 6400 1151 3549 4 0 1218 3928 4 4 1283 4325 4 8 1347 4739 5 3 1409 5169 5 8 6900 1167 3821 4 3 1232 4207 4 7 1295 4608 5 2 1357 5026 5 6 1417 5460 6 1...

Page 18: ...at this cfm is above unit maximum cfm limit NOTES 1 Heaters are rated at 208 240 v and 480 v 2 The factory assembled horizontal adapter substantially improves fan performance See Fig 23 3 The static p...

Page 19: ...r or two position damper control The damper motor will be energized at terminal TR and the damper will drive open to minimum vent position The damper motor will stop and the damper will remain in the...

Page 20: ...at least twice during each heating and cooling season and when ever the filters become clogged with dust and lint Replace filters with the same dimensional size and type as originally provided when ne...

Page 21: ...see Fig 25 4 Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed Increas ing fan speed increases load on motor Do not exceed maxi mum speed specifie...

Page 22: ...damper will go to the vent position 3 Adjust the vent position with the minimum position adjustment on the economizer motor control module See Fig 17 4 Set the system selector switch to COOL position...

Page 23: ...age and temperature sensing device are required Connect temperature sensing device to service port on suction line and insulate it so that outdoor ambient temperature does not af fect reading Indoor a...

Page 24: ...ts frost build up and turns off the compressor allowing the coil to clear Once the frost has melted the compressor can be reenergized X RELIEF DEVICES All units have relief devices to protect against...

Page 25: ...k valve 4 The refrigerant then flows through the 4 way valve accumulator and back to the compressor NOTES 1 Hot gas from compressor flows through the 4 way valve and is directed to the indoor coil hea...

Page 26: ...nt short cycling on com pressor overload and safety devices Before replacing CLO check these devices 9 Remove jumper between terminals RC an RH 1 AHA Adjustable Heat Anticipator BRK W AT Breaks With A...

Page 27: ...Fig 33 Typical Label Diagram Schematic 542J180 208 230 V 60 Hz Unit Shown ELECTRIC HEAT AHA SETTING 208 240 V Amps 208 240 V kW 1st 2nd A 72 82 25 7 34 2 1 00 0 52 B 117 135 42 3 56 1 1 00 0 78 27...

Page 28: ...Fig 33 Typical Label Diagram Schematic 542J180 208 230 V 60 Hz Unit Shown cont 28...

Page 29: ...TROUBLESHOOTING CHART HEATING CYCLE ODT Outdoor Temperature 29...

Page 30: ...TROUBLESHOOTING CHART COOLING CYCLE Copyright 1997 Carrier Corporation CATALOG NO BDP 3354 237...

Page 31: ......

Page 32: ...G ORIFICE AND VERIFY SET SCREW IS TIGHT M VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED START UP ELECTRICAL SUPPLY VOLTAGE L1 L2 L2 L3 L3 L1 COMPRESSOR AMPS COMPRESSOR NO 1 L1 L...

Reviews: