Table 6 Compatible Actuating Devices
Part No.
Manufacturer Description
4452
Panasonic
Conventional photoelectric smoke detector
4375
Panasonic
Conventional heat detector 60⁰ C
4376
Panasonic
Conventional heat detector 80⁰ C
6295
Panasonic
Conventional enclosed heat detector 60 degrees
6296
Panasonic
Conventional enclosed heat detector 80 degrees
6297
Panasonic
Conventional enclosed heat detector 100 degrees
6298
Panasonic
Conventional enclosed heat detector 120 degrees
MRCSRR
Menvier
Red MCP complete with 470 / 680 Ohm alarm
resistance.
The typical zone input circuit is shown in Figure 5
Figure 5 Zone Input Circuit
If the zone input is not used, an EOL resistor must be installed on the zone input terminals, otherwise
a fault condition will be generated. The zone EOL resistor type is 3k9, 1W, 1%, metal film.