background image

 

FT1-SB System Manual 

MA370 Iss. 2 

 

 

 

 

 

 

 

  

 

15 

4.1.2  Wiring 

The wiring of FT1-SB must be carries out according to the block wiring diagram shown in 

Figure 6, page 13. 

4.1.3  Visual inspection 

Full functional testing and visual check is carried out in the factory for FT1-SB before delivery. Upon 

completion of installation and prior to applying power, a visual inspection should be carried out to 

ensure:  
 

  All detectors are connected with the correct polarity. 

  End of Line resistor 3K9 is fitted in the last detector or MCP in the zone circuit. 

  Where the supervised output is used, the end of line resistor 47K is fitted on the last device 

in the output circuit as shown in Figure 4.  

 

The connection of mains power to the power supply is correctly terminated

.  

 

4.2  Commissioning 

4.2.1  Power ON  

The Power ON Procedures to be carried out during on-site commissioning as follow:  

1.  Turn ON the circuit breaker that connects mains power to FT1-SB power supply. Check that 

the green mains “Power ON” LED on the power supply module is illuminated. 

2.  On the front Display, check that only the green ‘Power ON” LED is illuminated, all other LED 

indicators should be extinguished 

3.  Measure the DC voltage on the power supply output bV and -V. The voltage should 

be 24Vdc +/- 0.2V. If the voltage requires adjustment, locate the “+V ADJ” trim pot on the 

front of the power supply module and adjust the voltage to be within tolerance. 

 

4.2.2  Alarm & Fault Test (Test controls) 

FT1-SB front display provides 3 controls for the zone circuit; alarm test, fault test and disable. The 

alarm test and fault test procedures may be carried out as shown below: 

1.  Press the alarm test control button, check: 

  Alarm LED flashing 

  Buzzer  is On 

  Alarm relays and supervised output activated. 

2.  Press the Silence Buzzer control, the buzzer stops sounding. 
3.  Press Disable, all alarm outputs de-activate, the alarm LED remains flashing 
4.  Press the “Reset” button, alarm relays de-energise and the alarm LED turns off. 
5.  Re-Press the ‘Disable” control to reenable the system. 
6.  Press the fault test button and check the following: 

  Fault LED is flashing 

  Buzzer is On 

  Fault relay is de-energised (normally energised) 

Summary of Contents for Firetracker FT1-SB

Page 1: ...SYSTEM MANUAL FT1 SB Single Zone FireAlarm System...

Page 2: ...Issue Date Description Written By Checked By Draft 0 2 9 2008 Original Document A Shenouda C Orr Issue 1 4 11 11 Update drawing in figure 7 A Shenouda A Shenouda Issue 2 18 11 19 Change Brooks address...

Page 3: ...OLS AND INDICATIONS 9 3 1 LED FLASH FUNCTIONS 9 3 2 BUZZER INDICATING PATTERN 9 3 3 CONTROL FUNCTIONS 10 3 4 CONTROL OUTPUTS 10 3 4 1 Non supervised outputs 10 3 4 2 Supervised Output 11 3 5 ZONE INPU...

Page 4: ...e Input Circuit 12 Figure 6 FT1 SB Block Wiring Diagram 13 Figure 7 Control Termination Module Power Supply mounting 14 Figure 8 FT1 SB Front Display typical mounting 14 TABLE LIST Table 1 FT1 SB Spec...

Page 5: ...ors and auxiliary outputs are available on the termination module The termination module is interfaced to the display module via RS232 Only 4 wires are required to connect the front display module to...

Page 6: ...tact 30V 0 5 Amp Disable Relay Output Changeover zone disable relay contact 30V 0 5 Amp Dimensions Display Module 96mm x 96mm x 72mm H W D Termination Module 90mm x 106mm x 58mm H W D Power Supply 90m...

Page 7: ...lity is segregated and includes a separate controls and LED indicators for each function i e alarm test fault test and disable isolate A Power ON and Common Fault indicators are provided to indicate t...

Page 8: ...odule The termination and control module to be mounted on a DIN rail at a convenient location within the switchboard cabinet The module as shown in Figure 2 above provides the termination point for al...

Page 9: ...ow Figure 3 Din rail Power supply Features Universal AC input Short circuit Overload Over voltage Protections Can be installed on a 35mm DIN rail LED indicator for power on No load power consumption C...

Page 10: ...nction Power On Steady On Power On Zone Alarm Flashing Steady on Alarm Test True Alarm Zone Fault Flashing Steady Fault Test Open or short circuit fault Zone Disable Steady Zone outputs disabled Commo...

Page 11: ...tected and verified before the alarm relays and buzzer become active Fault Test Fault LED flashes once every second Fault relay activate Perform zone fault test It takes approximately 3 seconds for th...

Page 12: ...terminals on the control termination module The EOL resistor type is 47K 1 2W or 1W 1 metal film 3 5 Zone Input The zone input specifications and compatible devices are listed in Table 5 and Table 6...

Page 13: ...296 Panasonic Conventional enclosed heat detector 80 degrees 6297 Panasonic Conventional enclosed heat detector 100 degrees 6298 Panasonic Conventional enclosed heat detector 120 degrees MRCSRR Menvie...

Page 14: ...5A 24VDC 24VDC 0 5Amp SUPERVISED CONTACTRATING 0 5A 24VDC CONTACTRATING 0 5A 24VDC CONTACTRATING 0 5A 24VDC CONTACTRATING 5A 24VDC 240VAC ALARM OUTPUTS FAULT OUTPUTS N Figure 6 FT1 SB Block Wiring Dia...

Page 15: ...FT1 SB System Manual MA370 Iss 2 14 Figure 7 Control Termination Module Power Supply mounting Rear Front Figure 8 FT1 SB Front Display typical mounting...

Page 16: ...er ON LED on the power supply module is illuminated 2 On the front Display check that only the green Power ON LED is illuminated all other LED indicators should be extinguished 3 Measure the DC voltag...

Page 17: ...ted zone open circuit and check the following Zone fault LED and common fault LED Illuminate steady Buzzer is pulsing once every 3 seconds Fault relay on the Control Termination Module is de energized...

Page 18: ...cident neglect misuse unauthorized dismantling or contamination howsoever caused incorrect installation careless handling or where repairs have been made or attempted by others Onsite warranty repairs...

Page 19: ...ent Abbotsford VIC 3067 Ph 03 9879 5294 SA P O Box 101 Woodville SA 5011 729A Port Road Woodville SA 5011 Ph 08 8347 0000 QLD P O Box 511 Archerfield QLD 4108 2 49 Boyland Ave Coopers Plains QLD 4108...

Reviews: