FT1-SB System Manual
MA370 Iss. 2
10
3.3 Control Functions
Table 4 FT1-SB Control Buttons
Control
Condition
Description
Buzzer Mute
Buzzer Off
Silences the panel buzzer until a new fault
or alarm occurs
Reset
System resetting
Reset active alarm or fault
Disable active test mode.
Note: If alarm or fault condition still active,
the alarm or fault will re-activate
Alarm Test
Alarm LED flashes once
every second.
All alarm outputs active
Perform zone alarm test. It takes
approximately 3 seconds for the alarm
condition to be detected and verified before
the alarm relays and buzzer become active
Fault Test
Fault LED flashes once
every second
Fault relay activate
Perform zone fault test. It takes
approximately 3 seconds for the fault
condition to be detected and verified before
the fault relay and buzzer become active
Disable
Disable LED Steady on
Disable all alarm or fault outputs
Energise disable relay
Zone alarm or fault LED remains
illuminating
3.4 Control Outputs
3.4.1 Non-supervised outputs
The non-supervised outputs include the following.
•
Alarm condition relay output, 2 sets of changeover relay contacts
•
Fault condition relay output, 2 sets of changeover relay contacts
•
Disable condition relay output. 1 set of changeover relay contacts