1  Introduction 

1.1  Important Information 

 
The Brooks Firetracker FT1-SB is a customised single zone conventional fire alarm panel designed 

to protect switch boards. In conjunction with compatible smoke and/or heat detectors and auxiliary 

devices, FT1-SB provides a complete single zone automatic fire detection and alarm system. FT1-

SB is designed to meet the requirements of the Australian standard AS7240.2 and for specific use 

in non-critical switchboard applications such as main switch boards and motor control panels.  
 
FT1-SB consists of 3 basic modules: 
 

1. 

Display Module

: includes all controls and indicators and provides the user interface to 

control and monitor the FT1-SB system. The display module is designed to be mounted on 

the front door of a switch board and fits into the standard square cut-out 90 x 90 mm in any 

switch board door cabinet. This provides full control of the system without the requirements 

to enter the panel and avoid exposure to live parts 

2. 

Termination & Control Module

:  housed in a DIN  rail enclosure and mounted on the 

equipment gear tray inside the switch board cabinet. The termination of all detectors and 

auxiliary outputs are available on the termination module. The termination module is 

interfaced to the display module via RS232. Only 4 wires are required to connect the front 

display module to the termination module allowing flexibility of mounting location within the 

switchboard cabinet. 

3. 

Power supply

: DIN rail switch mode power supply mounted on the equipment gear tray 

next to the termination and control module.  

 

1.2  System Overview 

 
Brooks FT1-SB is specifically designed for use in switchboard applications where fire detection is 

required within the switchboard cabinet itself rather than protecting the room within which the 

switchboard is located. The modular design of FT1-SB allows for easy mounting utilising the same 

techniques as originally used in the switchboard design, i.e. standard meter case format and DIN 

rail mounting.  
 
The system continually monitors the zone circuit for normal, alarm and fault (short or open circuit) 

conditions. The system provides alarm, fault and disable (isolate) voltage free contacts and a fully 

supervised 24V

DC 

switched output to initiate external ancillary devices or as an input to local system 

monitoring such as a building management system.  
 
FT1-SB system utilises a non-battery backed 24V

DC

 power supply. The DIN rail switch mode power 

supply has a wide range of mains input voltages and an adjustable 24V

DC

 output. 

 
 
 
 
 
 

Summary of Contents for Firetracker FT1-SB

Page 1: ...SYSTEM MANUAL FT1 SB Single Zone FireAlarm System...

Page 2: ...Issue Date Description Written By Checked By Draft 0 2 9 2008 Original Document A Shenouda C Orr Issue 1 4 11 11 Update drawing in figure 7 A Shenouda A Shenouda Issue 2 18 11 19 Change Brooks address...

Page 3: ...OLS AND INDICATIONS 9 3 1 LED FLASH FUNCTIONS 9 3 2 BUZZER INDICATING PATTERN 9 3 3 CONTROL FUNCTIONS 10 3 4 CONTROL OUTPUTS 10 3 4 1 Non supervised outputs 10 3 4 2 Supervised Output 11 3 5 ZONE INPU...

Page 4: ...e Input Circuit 12 Figure 6 FT1 SB Block Wiring Diagram 13 Figure 7 Control Termination Module Power Supply mounting 14 Figure 8 FT1 SB Front Display typical mounting 14 TABLE LIST Table 1 FT1 SB Spec...

Page 5: ...ors and auxiliary outputs are available on the termination module The termination module is interfaced to the display module via RS232 Only 4 wires are required to connect the front display module to...

Page 6: ...tact 30V 0 5 Amp Disable Relay Output Changeover zone disable relay contact 30V 0 5 Amp Dimensions Display Module 96mm x 96mm x 72mm H W D Termination Module 90mm x 106mm x 58mm H W D Power Supply 90m...

Page 7: ...lity is segregated and includes a separate controls and LED indicators for each function i e alarm test fault test and disable isolate A Power ON and Common Fault indicators are provided to indicate t...

Page 8: ...odule The termination and control module to be mounted on a DIN rail at a convenient location within the switchboard cabinet The module as shown in Figure 2 above provides the termination point for al...

Page 9: ...ow Figure 3 Din rail Power supply Features Universal AC input Short circuit Overload Over voltage Protections Can be installed on a 35mm DIN rail LED indicator for power on No load power consumption C...

Page 10: ...nction Power On Steady On Power On Zone Alarm Flashing Steady on Alarm Test True Alarm Zone Fault Flashing Steady Fault Test Open or short circuit fault Zone Disable Steady Zone outputs disabled Commo...

Page 11: ...tected and verified before the alarm relays and buzzer become active Fault Test Fault LED flashes once every second Fault relay activate Perform zone fault test It takes approximately 3 seconds for th...

Page 12: ...terminals on the control termination module The EOL resistor type is 47K 1 2W or 1W 1 metal film 3 5 Zone Input The zone input specifications and compatible devices are listed in Table 5 and Table 6...

Page 13: ...296 Panasonic Conventional enclosed heat detector 80 degrees 6297 Panasonic Conventional enclosed heat detector 100 degrees 6298 Panasonic Conventional enclosed heat detector 120 degrees MRCSRR Menvie...

Page 14: ...5A 24VDC 24VDC 0 5Amp SUPERVISED CONTACTRATING 0 5A 24VDC CONTACTRATING 0 5A 24VDC CONTACTRATING 0 5A 24VDC CONTACTRATING 5A 24VDC 240VAC ALARM OUTPUTS FAULT OUTPUTS N Figure 6 FT1 SB Block Wiring Dia...

Page 15: ...FT1 SB System Manual MA370 Iss 2 14 Figure 7 Control Termination Module Power Supply mounting Rear Front Figure 8 FT1 SB Front Display typical mounting...

Page 16: ...er ON LED on the power supply module is illuminated 2 On the front Display check that only the green Power ON LED is illuminated all other LED indicators should be extinguished 3 Measure the DC voltag...

Page 17: ...ted zone open circuit and check the following Zone fault LED and common fault LED Illuminate steady Buzzer is pulsing once every 3 seconds Fault relay on the Control Termination Module is de energized...

Page 18: ...cident neglect misuse unauthorized dismantling or contamination howsoever caused incorrect installation careless handling or where repairs have been made or attempted by others Onsite warranty repairs...