27
FUNCTIONING
•
ON/OFF:
The On/Off of the controller is made by pushing the button P1
The state OFF is signaled through the led L1
•
FUNCTIONING Modality
-
MANUAL
: advice signal
MAN
The fan is at the set speed independently by the Probe’s temperature
-
AUTOMATIC
: advice signal
AUT
The Fan starts at the set up speed when the trmperature is higher than the setted Thermostat
SET
-
PROPORTIONAL
: advice signal
PROP
The fan changes its speed according to the temperature in the range
SET ÷ SET+DEL
•
STANDBY Function
: if parameter
Stb =1
If the device is
OFF,
and the temperature is higher than the value of thermostat
TSI
-
The device goes in
ON
automatically
•
SAFETY
Function
: if the parameter
SIC = 1
If the probe’s temperature is higher than value of thermostat
TSI
And the fan is
OFF
in
MANUAL
Modality
-
The device goes automatically in the Proportional Modality waiting 10 seconds.
SAFETY FAN Function
: if the parameter
SAF = 1
If the probe’s temperature is higher than value of thermostat
TSA
-
The Fan is OFF
•
ALARM Function:
If probe’s temperature is higher than the value of thermostat
TAL
and the parameter
Enb = 1
-
The acoustic signal is activated
-
This signaling can be deactivated for 5 minutes by pushing a button
-
After 5 minutes, if there’s again the condition of alarm, it is activated again.
MAIN MENU
•
FUNCTIONING Modality Selection
-
Press
P4
key to see the current modality: it’s signaled by the display and the led
-
Pressing again the
P4
key, you can select cyclically one of three functioning modality
MAN,
AUT
,
PRP
signaled on the display and by
the specific led.
-
The setting is automatically memorized after 4 seconds
-
The
L5
shows the status of the Fan
•
SPEED Selection
-
Pressing
P2 or P3
keys the setting of the current fan speed is visualized or modified
-
P0
= Off (only in Manual);
P1
= Minimum Speed;
P10
= Maximum Speed
-
This function is not available in the PROPORTIONAL Modality
-
In the AUTOMATIC Modality the speeds that can be set are
P1 ÷ P10
FAILURE OR ALARM SIGNALS
The controller can signal the failure of the probe blinking message for the failure signal:
-
Lo
: indicates a low temperature (temperature under 0°C):
Probe Open or Disconnected
-
Hi
: indicates a high temperature (temperature over 180°C):
Probe in Short Circuit
ATTENTION
-
Avoid join together the probe’s cables with power’s cables.
-
Provide the system’s feeding with a bipolar switch according to the actual rules and with opening distance of the contacts of at least 3
mm for each pole.
-
Installation and the electrical connection of the device have to be made by experienced personal and with appropriate equipping.
-
Before the connection be aware that the electrical feeding is not connected.
SECONDARY MENU
It allows to modify the functioning parameters of the controller.
-
To enter the MENU push together buttons
P2
and
P3
for about 5 seconds.
-
To scroll the code list use the button
P2
or
P3
-
To show the parameter’s value push the button
P4
-
To modify the parameter’s value push the buttons
P2
or
P3
-
To visualize again the code list and memorize push the button
P4
-
To exit and memorize wait for about 10 seconds.
The parameters are described in the following table
SECONDARY MENU PARAMETERS
CODE
MIN
DEFAULT
MAX
Temperature Fan Activation
SET
30º
45º
99º
Temperature Fan Activation Hysteresis
iSt
1º
2º
35º
ALARM Temperature Activation
TAL
100º
120º
180º
INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS
INSERTS
EN
Summary of Contents for BRISTOL
Page 103: ...102 ...