The  appliance  is  furnished  with  (G20)  gas  function

following  the  Technical  label,  and  the  constructor

already  regulates  it.  If  you  make  a  new  regulation,

like exchanging the gas valve, or a gas transforma-

tion  from  Methane  to  GPL  or  reversed,  this  regula-

tion  has  to  be  done  from  a  Technical  service

Assistance or by the manufacture

Gas  methane  G  20(20mbr);  nominal  &  minimum

pressure regulation.  

- Open the gas tap put the electrical plug under the

appliance then pushes the start button and put to the

max power.

Alimentation pressure 

- Loosen the pressure screw (1) connect the mano-

meter  and  verified  the  pressure  value  is  included

between 17/25mbar (like indicated in the table) then

close the screw after that the manometer tube is pul-

led away.

- Loosen the pressure screw (2) connect the mano-

meter  verified  the  nominal  and  minimum  pressure

values are as specified in the table.

Nominal pressure

With the appliance in function at a max power loosen

the outlet pressure screw (2) then connect the mano-

meter and verified that the nominal pressure values

are as specified in the table (Nozzle Pressure). In the

GPL function, only for the 3+ categories the regulator

has to be out of service fastening clockwise the adju-

stment screw (1) at an immediately inferior value to

the alimentation max pressure.

At  verification  done,  take  away  the  manometer  and

fasten the screw.

Minimum pressure

- Lift (On) the first switch to the left on this unit, so it

is working to "reduced power".

- Turn the idle screw (4).

Turn the screw counterclockwise, the pressure

increases, turning clockwise, the pressure decreases.

- Once adjusted, lowering the switch (off), disconnect

the  manometer  from  the  pressure  tap  and  replace

the screw pressure reading.

- Completion of the adjustments, seal with a drop of

paint the screw on the regulator and the modulator.

-  Disconnect  the  manometer  from  the  pressure  tap

and replace the screw.

Regulation  GPL  butane  G30  (29mbar)  and

Propane  G31  (37mbar).  Minimum  and  nominal

pressure.

- Open the gas taps put the electrical plug under the

appliance then push the start button and put to the

max power.

Alimentation pressure

- Loosen the pressure screw (1) connect the mano-

meter  and  verified  the  pressure  value  is  included

between 29 mbar with the Butane and 37 mbar with

Propane  then  close  the  screw.  In  the  case  that  the

net  pressure  is  low,  operate  on  the  low-pressure

regulator that is put on the Gas tank.

-  Verified  that  the  establishment  GPL  vaporization

capacity is sufficient.

Nominal pressure

With the appliance in function at a max power loosen

the outlet pressure screw (2) then connect the mano-

meter and verified that the nominal pressure values

are as specified in the table (Nozzle Pressure). In the

GPL function, only for the 3+ categories the regulator

has to be out of service fastening clockwise the adju-

stment screw (1) at an immediately inferior value to

the alimentation max pressure.

At  verification  done,  take  away  the  manometer  and

fasten the screw.

REGOLATION

Summary of Contents for 2620970

Page 1: ...DOOR GAS HEATER STRATOS 3 0 5 0 7 0 9 0 BROMIC COM PLUMBING 1300 276 642 A member of the Bromic Group July 2019 V1 PRODUCT IMAGE INSTALLATION INSTRUCTION AND SERVICE MANUAL BROMIC FLUED INDOOR GAS HEA...

Page 2: ...manual may not be reproduced in any form without prior written consent from Bromic Plumbing Pty Ltd This manual contains important information about the assembly operation and maintenance of Blow Hea...

Page 3: ...maintenance pag 25 Appliance clean out pag 25 Components replacement pag 26 Disassembly reassembly of the casing pag 30 Eventual anomalies remedies pag 30 Useful information pag 32 4 GENERAL INDEX GEN...

Page 4: ...ty of the contents In case of discrepancies contact the Agency that sold the appliance The APPLIANCE must be used as intended by the Manufacturer and for the purpose for which it was expressly built T...

Page 5: ...ll not consent the right identification of the apparatus The appliance is a gas radiator that heat up the atmosphere It has an intake of air that goes in the combustion chamber type C The appliance is...

Page 6: ...Flued Indoor Gas Heater Instruction Manual 6 July 2019 V1 7 GENERAL STRUCTURE...

Page 7: ...84 Floor Standing Kit 3 0 233628 2620985 Floor Standing Kit 5 0 233629 2620986 Floor Standing Kit 9 0 233631 2620987 HT Armaflex 32mm 70000840 2620988 HT Armaflex 54mm 70000850 2620989 Stratos 32mm Fl...

Page 8: ...Flued Indoor Gas Heater Instruction Manual 8 July 2019 V1...

Page 9: ...ient temperature degrees centigrade unit scale data transmission DESCRIPTION OF ICONS 1 operation at MAX power 2 operation at MIN power 3 data transmission between the device and the Wireless command...

Page 10: ...ction pipe L 500mm 32mm Mod 3 0 5 0 54mm Mod 7 0 9 0 1 exhaust pipe L 500mm 32mm Mod 3 0 5 0 54mm Mod 7 0 9 0 1 Single outer end piece anchors 32mm Mod 3 0 5 0 54mm Mod 7 0 9 0 1 Document envelope 1 O...

Page 11: ...Flued Indoor Gas Heater Instruction Manual 11 July 2019 V1 12 INSTALLER WEIGHT DIMENSION...

Page 12: ...ubes there are mate rials that can support the heath second check if the wall is made of the right material and can support the appliance weight Verified if around the exhaust fumes tubes there is no...

Page 13: ...ht it exist a spacing bar so that you can see the tubes we recommend that the exhaust tubes have to have a good insulation using materials that have also a resistant of more 200 C ex HT Armaflex of te...

Page 14: ...25 mm then eliminate the excess parts The cut must be perpendicular to the pipe axis being very careful not to deform these After cutting carefully remove any burrs To make it easier to fit pipes wit...

Page 15: ...al from the out side Insert in the wall the assembled group adapter con nection angles and curves Position the exhaust intake tubes at thread outside wall being real careful that the short tube is alw...

Page 16: ...Flued Indoor Gas Heater Instruction Manual 16 July 2019 V1...

Page 17: ...hole A for the suction and exhaust pipes assemble the side brackets 1 with the template 2 supports 6 and the adjustment screws 7 so as to create a single structure 5 move the single structure up again...

Page 18: ...2 to length equal to the wall thickness Fit the internal tube 2 inside the opening cut in the wall Fit the metal plate 5 to the inside of the wall using the 4 screws with anchors for wooden walls prov...

Page 19: ...iance for eventuating any problems use a nipples After the gas connection is done do the first seal tests GAS CONNECTION This apparatus is equipped with a cable with plug for connection to the mains p...

Page 20: ...prevent water overflowing with consequent damage to or malfunction of the appliance Only fill the tray with water Avoid all other liquids that could damage the tray or cause appliance malfunctions Af...

Page 21: ...ket or move the master switch to off and then to on At the start verified that the gas pressures are as under the Table The gas pressure value has to be as in the table The apparatus execute a stop an...

Page 22: ...ws M5 2 then slip off the cap and the burner group 3 Unscrew the screws 4 and the burner 5 Unscrew the 3 injectors 6 change them with the new ones Be real careful when you fasten the injec tor check o...

Page 23: ...and fasten the screw Minimum pressure Lift On the first switch to the left on this unit so it is working to reduced power Turn the idle screw 4 Turn the screw counterclockwise the pressure increases t...

Page 24: ...as tap Wait that the appliance gets cold completely Cover clean The only cleaning that is required by the owner involves removing the cover and wiping it clean the dust which may have collected Do not...

Page 25: ...ck if there are deposits or condensation within the pipes pressure measurement Fan combustion air pressure switch Exhaust fumes pressure Blow disconnect the switch and test it otherwise may be damaged...

Page 26: ...ve to be replaced with another of the rapid type F1AT 250 V Comburant air fan replacement Follow the indication to replace the comb rent air fan Take off the electrical connectors from the motor Take...

Page 27: ...ostat unit in reverse fitting sequence The safety thermostat trips if the convection fan is not working properly or anomalous overheating occurs and or the outflowing air temperature reaches over 107...

Page 28: ...Follow the indication to replace the Pressure switch Extract the pressure switch 1 from support 2 Take off the tubes 3 4 and the electrical connec tors from the pressure switch Unscrew the stirrup su...

Page 29: ...uly 2019 V1 30 CUSTOMER SERVICE Disassembly cover Disassembly the casing Remove the cup 3 Unscrew the screw 2 Remove the outside skirt 1 completely To replace the skirt do the reversed sequence DISASS...

Page 30: ...Flued Indoor Gas Heater Instruction Manual 30 July 2019 V1 31 CUSTOMER SERVICE...

Page 31: ...Flued Indoor Gas Heater Instruction Manual 31 July 2019 V1 USEFUL INFORMATION 32 CUSTOMER SERVICE...

Page 32: ...Flued Indoor Gas Heater Instruction Manual 32 July 2019 V1 33 NOTE NOTE...

Reviews: