38
Renovent Sky 200 Rev. C
67(312 '(6&5,37,21
FACTORY SETTING
RENOVENT SKY
ADJUSTING RANGE
67(3
1
$LUÀRZUDWHPRGH
/
50 m
3
/h
0 m
3
/h or 50 m
3
/h
2
$LUÀRZUDWHPRGH
100 m
3
/h
50 m
3
/h - 200 m
3
/h
5 m
3
/h
3
$LUÀRZUDWHPRGH
125 m
3
/h
50 m
3
/h - 200 m
3
/h
5 m
3
/h
4
$LUÀRZUDWHPRGH
150 m
3
/h
50 m
3
/h - 200 m
3
/h
5 m
3
/h
5
Bypass temperature
22,0 °C
15,0 °C - 35,0 °C
0,5 °C
6
Bypass hysterese
2,0 °C
0,0 °C - 5,0 °C
0,5 °C
7
Operation bypass valve
0
0 (= Automatic)
1 (= Bypass valve closed)
2 (= Bypass valve open)
8
Central h
heat recovery
OFF
ON (= Central heat recovery on)
OFF (= Central heat recovery off)
9
Imbalance permissible
ON
ON (=
ÀRZUDWHVXSSO\HTXDOVH[WUDFW
)
OFF (= imbalance permissible)
10
Fixed imbalance
0 m
3
/h
-100 m
3
/h - 100 m
3
/h
1 m
3
/h
67(312
.
'(6&5,37,21
FACTORY SETTING
5(129(176.<3/86
ADJUSTING RANGE
67(3
11
Heater
0
0 (= no additional heater)
1 (= additional preheater)
2 (= postheater)
12
Temperature postheater
21,0 °C
15,0 °C - 30,0 °C
0,5 °C
13
Selection input 1
0
0 (= normally open contact)
1 (= 0 - 10V input active)
2 (= normally closed contact)
3 (= input 1/ bypas open
¼
12V;
bypass closed
¼
0V)
4 (= input 1/ bypas open
¼
0V;
bypass closed
¼
12V)
14
Minimum voltage input 1
0,0 V
0 Volt - 10 Volt
0,5 V
15
Maximum voltage input 1
10,0 V
0 Volt - 10 Volt
0,5 V
16
Conditions
switching input 1
0
0 (= off)
1 (= on)
2 (=
2QLIFRQGLWLRQVE\SDVVRSHQVDWLV¿HG
3 (= Bypass control)
4 (= Bedroom valve)
17
Supply fan mode
switching input 1
5
0 (= Input fan off)
1 (=
$EVROXWHPLQÀRZUDWHP
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6 (=
0D[LPXPÀRZUDWH
)
7 (= No input fan activation)
18
Extract fan mode
switching input 1
5
0 (= Extract fan off)
1
$EVROXWHPLQÀRZUDWHP
3
/h)
2 (= Flow rate mode 1)
3 (= Flow rate mode 2)
4 (= Flow rate mode 3)
5 (= Multiple switch)
6
0D[LPXPÀRZUDWH
7 (= No extract fan activation)
Chapter 12 Setting values
Summary of Contents for Renovent Sky 200
Page 1: ...Renovent Sky 200 Plus WWW BRINKAIRFORLIFE NL 614485 C INSTALLATION INSTRUCTIONS English ...
Page 2: ......
Page 17: ...Renovent Sky 200 Rev C 13 Chapter 5 Installation A A X A 1 2 3 4 A t 60 mm t A ...
Page 18: ...14 Renovent Sky 200 Rev C Chapter 5 Installation A A X A 1 2 3 4 A t 60 mm t A ...
Page 32: ...28 Renovent Sky 200 Rev C Chapter 8 Maintenance 12 13 14 15 16 4x 3x 17 ...
Page 47: ......