I E16x442 Rev: 00
Page 65 of 73
P13.05
Delay of Antivalence Alarm
Range: 0 .. 9
To avoid unnecessary Antivalence Alarms due to shifted trip release signals
at the voter inputs a delay may be introduced.
Antivalence alarm will then be released only if the time shift between the
signals exceeds the set delay.
Setting
0 : no delay
1 : delay = 100 milliseconds
2 : delay = 500 milliseconds
3 : delay = 1 second
4 : delay = 2 seconds
5 : delay = 3 seconds
6 : delay = 5 seconds
7 : delay = 15 seconds
8 : delay = 30 seconds
9 : delay = 60 seconds
P13.06
Setpoint SPV4
Range: 00001 .. 99999 [RPM]
Depending on setting of P13.00, SPV4 controls the activity of voter 4 or con-
trols directly the output LO4.
SPV4 is set in terms of RPM.