Parameter Group P01.xx of Monitor E1665
Input Scaling and Measurement Configuration
Parameter No.
Meaning of Parameter
Setting Range of Parameter
Description of Parameters and their Settings
P01.00
Reserved for future applications
Description of Scaling:
Scaling defines the relationship between the input signal frequency (in terms
of Hz), and the corresponding display (in terms of RPM).
Of course, they must refer to the same operation level. This reference point
is recommended close to the high end of the intended operation range. In
later operation, however, it may be overrun without error.
Example:
1500 Hz corresponds to 3000 RPM :
Step P01.01 : setting 01500
Step P01.03 : setting 03000
P01.01
Nominal Input Frequency [Hz]
Range: 00001 .. 99999
See description of Scaling.
P01.02
Decimals for P01.04, P04.00,
P05.00 and for
PROFIBUS Speed Data Output
Range: 0 .. 1
Setting
0 : Setting range for P01.04, P04.00, P05.00 : 00001 to 99999 RPM
1 : Setting range for P01.04, P04.00, P05.00 : 0000.1 to 9999.9 RPM
P01.03
Nominal speed [RPM]
Range: 00001 .. 99999
See description of Scaling.
P01.04
Lower Limit of the Speed
Range
Range as defined in P01.02
If the monitored speed falls below the value entered here the measured val-
ue is given as 0 both for the display and the alarms. The lower limit of the
speed range is entered in units of RPM.