Setting Manual Overrides
Each relay can be manually overridden to force it either on or off. To access these options,
navigate to
Settings > Relay Settings > Relay #
. Under “Relay Override Status”, selecting “On”
will open a pop-up window to force the relay into its active state – as if its setpoint was
exceeded. Use the arrows to adjust the duration for which the override should last, or select
“Manual” to keep the override active indefinitely. Selecting “Off” will open the same pop-up
window to force the relay into its inactive state – as if no gas was detected. Selecting “None”
will return the relay to its normal operating state. Any scheduled automatic overrides or gas
related activity will take effect at this time. If neither condition is present, the off-delay timer will
begin. Note that manual overrides take precedence over normal operation and automatic
overrides.