Factory Default Settings
Unless otherwise specified on the order form, the following settings will be used to configure
the control panel.
Setting
Default
Sensors
All Sensors Configured
Relays
4 Relays
Relay 1
(Low Alert)
All Sensors
On-Delay
1 minute
Off-Delay
1 minute
Setpoint
35 PPM CO / 1.0 PPM NO
2
Activation Type
Single
Level
1
Relay 2
(Medium Alert)
All Sensors
On-Delay
0 minute
Off-Delay
1 minute
Setpoint
75 PPM CO / 3.0 PPM NO
2
Activation Type
Single
Level
1
Relay 3
(High Alert)
All Sensors
On-Delay
0 minute
Off-Delay
1 minute
Setpoint
100 PPM CO / 5.0 PPM NO
2
Activation Type
Single
Level
1
Relay 4
(Alarm)
All Sensors
On-Delay
15 minute
Off-Delay
0 minute
Setpoint
100 PPM CO / 5.0 PPM NO
2
Activation Type
Single
Level
1
Zone 1
All Relays
IOM03
Rev 1.1 – May 18, 2021
28