39
Operate
key. The former is actuated by an event, and the latter is actuated by manual control, no event
necessary.
Various types of jobs can be selected:
No Action: Do nothing.
Log Alarm: Record alarms
Log Event: Record events
Stop logging: Stop logging data.
Start logging: Start logging data.
Sound Buzzer: Sound the buzzer. It stops once any key is pressed.
DO Latch On: Set digital output / relay on, and then select Target from DO 1 to DO 6. The relay is
latched when it is activated.
DO Latch Off: Set digital output / relay off, and then select Target from DO 1 to DO 6. The relay is
latched when it is activated.
DO Process: Set digital output / relay on for process high or low, and then select Target from DO 1 to
DO 6. The relay is not going to be latched when it is activated.
Enable Timer: Start the timer, and then select Target from Timer 1 to Timer 6.
Disable Timer: Stop the timer, and then select Target from Timer 1 to Timer 6.
Preset Totalz: Start the totalizer with a preset value, then select Target from Tolz 1 to Tolz 6.
Reset Totalz: Reset totalizer into zero, and then select Target from Tolz 1 to Tolz 6.
Enable Totalz: Start the totalizer, then select Target from Tolz 1 to Tolz 6.
Disable Totalz: Stop the totalizer, then select Target from Tolz 1 to Tolz 6.
Preset Counter: Start the Counter with a preset value, then select Target from Cont1 to Cont6.
Reset Counter: Resets the counter into zero, and then select Target from Cont1 to Cont6.
Inc Counter: Increase the counter, and then select Target from Cont1 to Cont6.
Dec Counter: Decrease the counter, and then select Target from Cont1 to Cont6.
Log Report: Make the report for Counter and Totalizer. Choose this column, and then the report will be
presented as details described in
3.4 Event.
Reset MinMaxAve: In Report function, after logging the MinMaxAve data of AI and Math channels for
one day for example, then reset historical data in order to logging new data for the next day.
Hysteresis:
To avoid it been activated too often, the relay can set for no reaction in 0.1% to 10% of full
span ( Low Scale to High Scale ).
Note:
The sampling rate of the recorder is fixed at 200 milli seconds by the hardware, i.e. samples 5
measured data per second.. If the logging speed is set at 1 second in Instant mode, the recorder logs
using the last of five measured data values. For the same speed in Averaging mode, the recorder logs
using the average of the five measured data values. For the same speed in the Maximum or Minimum
mode, then the recorder logs using the maximum or minimum of the five measured data values..
Sampling Logging ( historical trend ) Display ( real time )
Instant 200mS the last of 5 measured data the last of 5 measured data
Averaged 200mS the average of 5 measured data the last of 5 measured data
Maximum 200mS the maximum of 5 measured data the last of 5 measured data
Minimum 200mS the minimum of 5 measured data the last of 5 measured data
◆
Press Back key to return to real-time display, all configurations will be memorized
◆
The
Digital output DO card
with 6 relays
can be set in Job1, Job2. It can be traced in
System Info
mode after installed into the Slot.
Summary of Contents for VR06
Page 1: ...User Manual Paperless Recorder VR06 UMVR061D Brainchild Electronic Co Ltd 4th Edition 10 2013 ...
Page 17: ...17 Figure 2 6 Figure 2 7 Figure 2 8 ...
Page 19: ...19 Figure 2 10 Figure 2 11 ...
Page 25: ...25 Digital input card DI181 Figure 2 21 Analog output card AO183I AO183V Figure 2 22 ...
Page 27: ...27 Figure 2 25 Figure 2 26 ...
Page 69: ...69 Make sure that RS 232 communication setting at the recorder and PC are equal ...
Page 86: ...86 7 Trouble shooting ...
Page 87: ...87 ...
Page 88: ...88 ...