Kodiak
Recirculating Chiller Technical Manual
Manual# 820-0043 Rev N, 11/25/2019
25
Water Filter (Option)
With a new system the filter quickly accumulates foreign matter introduced during system
setup. This can lead to a decrease in system performance in a short period of time. Inspect the
filter cartridge one day after you set up a new system to ensure the filter is clean and the system
runs at maximum capacity. After this initial filter inspection, check the filter weekly. For
replacement filters contact Boyd’s Customer Service at 781-933-7305.
Deionization Package
The cartridge life is a function of the user’s application. Check the water resistivity weekly
and change the cartridge as required. For replacement filters contact Boyd’s Customer Service
at 781-933-7305.
Control Box Fuse Replacement
This fuse is an inline fuse internal to the control box and should only be replaced by a qualified
technician. To replace the fuse remove the top and side panel on the unit and remove the two
fasteners holding the control box cover in place. Open the inline fuse holder. Remove blown
fuse and replace the cover. Use a 5x20 mm time lag fuse 3.15A 250V (Bussman P/N GDC-
3.15) or equivalent.
Periodic Maintenance
****CAUTION****
A qualified service technician must perform all service and maintenance internal to the chiller.