Kodiak
Recirculating Chiller Technical Manual
Manual# 820-0043 Rev N, 11/25/2019
23
rS—Remote Start Feature (option)
When it is set to off the chiller acts as if it does not have the remote start feature. By setting this
feature to NC (normally closed, or run on closed), the chiller will start when pins 4 and 5 on the six-
pin connector on the rear of the chiller are closed. The chiller will shut off when pins 4 and 5 are
open. By setting this feature to NO (normally open or run on open), the chiller will start when pins 4
and 5 are open. It will shut off when pins 4 and 5 are closed.
The electrical connector on the rear is an Amp Mate-N-Lok connector, part number 1-480705-0. Pins
1 and 2 are for the External Contact Feature (see page 15 of the manual) and pins 4 and 5 are for the
Remote Start Feature. The mating connecting is Amp part number 1-480704-0. The mating part
should use Amp pins for Mate-N-Lok connector, such as Amp part number 350552-1.
This chiller was shipped with remote start disabled. To activate the remote start feature:
1.
Enter the customer menu by holding both the “UP” or “DOWN” arrow keys for 3 seconds.
2.
Use the “SET” key to scroll to rS.
3.
The display toggles between “rS” and it’s current setting.
4.
Use “UP” or “DOWN” arrow key to toggle between “OFF”, “NO” and “NC”.
5.
Press “SET” to accept the setting on the display and continue ton the next feature.