Servicing
5
38
Installation and maintenance instructions for wall-mounted condensing gas boiler 600 - 28C • 01/2004
Subject to modifications resulting from technical improvements!
Boulter Buderus Ltd. • http://www.boulter-boilers.com
5.2
Fault codes
Code
Meaning
1C
Blinking fault code
: Flue gas temperature measured of more than 105 °C
Possible
cause
Action
1
Flue gas temperature too high
– Check the flue gas system
– Check the flue gas retarder
2
Flue gas sensor faulty
Check the wiring and connections of the flue gas sensor
and replace when necessary (see subsection 5.3.1)
Code
Meaning
2E
Non blinking fault code
: Water pressure in the system lower than 0.2 bar.
Possible
cause
Action
1
System pressure not checked in time
Top up the system to at least 1.0 bar
(see subsection 2.1.1)
2
Pressure sensor is defect
Replace pressure sensor
Code
Meaning
2F
Non blinking fault code
: The flow part of the bi-sensor did not detect a rise in the temperature of the central heating
water after a burner start
Possible
cause
Action
1
Resistance in the installation is too high
Check if not all (thermostatic) radiator valves are closed or
clogged with dirt
2
Water pressure is too low in the installation
Top up the system (see subsection 2.1.1)
3
Problem with the pump or pump cabling
(no circulation)
Check if the pump cabling is faulty or if the pump is stuck.
Replace pump when necessary (see subsection 5.3.6 and
subsection 5.3.7)
4
Bi-sensor is dirty or faulty
Check the bi-sensor for dirt. Measure if resistance over the
sensor is correct. If not replace bi-sensor (see subsection
5.3.8, subsection 5.3.9, subsection 5.3.10)
Code
Meaning
2P
Non blinking fault code
: Bi-sensor rises faster than 5 °K/sec.
Possible
cause
Action
1
Resistance in the installation is too high
Check if not all (thermostatic) radiator valves are closed or
clogged with dirt
2
Water pressure is too low in the installation
Top up the system (see subsection 2.1.1)
3
Problem with the pump or pump cabling
(no circulation)
Check if the pump cabling is faulty or if the pump is stuck.
Replace pump when necessary (see subsection 5.3.6 and
subsection 5.3.7)
4
Bi-sensor is dirty or faulty
Check the bi-sensor for dirt. Measure if resistance over the
sensor is correct. If not replace bi-sensor (see subsection
5.3.8, subsection 5.3.9, subsection 5.3.10)