7
Product information
Sense II – 6 720 818 367 (2015/10)
2.5
Technical data
Fig. 3
Dimensions in mm
2.6
Energy efficiency
The ErP and energy efficiency related product data can be
found in the operating instructions.
2.7
Temperature sensor characteristics
When measuring temperature sensors, observe the following
requirements:
•
Isolate the system before measuring.
•
Measure the resistance at the cable ends.
•
The resistance values represent average values and are
subject to tolerances.
2.8
Additional accessories
•
Sense I
as simple remote control
•
MC 400
: Module for a cascade of several heat sources
•
MM 100
: Module for one heating circuit with mixer,
cylinder primary circuit or constant heating circuit
•
MM 200
: Module for 2 heating circuits with mixer, cylinder
primary circuits or constant heating circuits
•
Greenstar Wiring Centre
: Module for systems with two
port valve (S-plan) or mid-position valve (Y-plan).
•
MS 100
: Module for solar DHW heating
•
MS 200
: Module for advanced solar systems (wall-
mounted installation only).
6 720 812 774-09.1O
auto
man
adv
menu
info
123
25
32
101
Scope of delivery
Measurements
123 × 101 × 25 mm
(
Nominal voltage
10 – 24 V DC
Rated power
(excluding
illumination)
9 mA
BUS interface
EMS 2
Control range
5 °C – 30 °C
Permitted ambient temp.
0 °C – 50 °C
IP rating
III
IP rating
•
For wall-mounted installation
•
in case of installation in the
heat source
•
IP20
•
IPX2D
Table 2 Technical data
°C
°C
°C
°C
– 20
2392
– 8
1562
4
984
16
616
– 16
2088
– 4
1342
8
842
20
528
– 12
1811
0
1149
12
720
24
454
Table 3 Resistance values for outside temperature sensors
°C
°C
°C
°C
8
25065
32
9043
56
3723
80
1704
14
19170
38
7174
62
3032
86
1421
20
14772
44
5730
68
2488
–
–
26
11500
50
4608
74
2053
–
–
Table 4 Resistance values for flow and DHW temperature
sensors