SM Series Heat Pump
SM Series Heat Pump
6 720 220 406 (2015/02)
Subject to change without prior notice
30
|
Water Quality
WATER QUALITY
ELECTRICAL
Refer to electrical component box layout.
(Figure #97)
Properly sized fuses or HACR circuit breakers must
be installed for branch circuit protection. See unit
nameplate for maximum fuse or breaker size.
Table 1: Water Quality
POTENTIAL
PROBLEM
Water Characteristic
Acceptable Value
Copper
Cupro-Nickel
pH (Acidity/Alkalinity)
7-9
7-9
SCALING
Hardness (CaCO3,
MgCO3)
< 350 ppm
< 350 ppm
Ryznar Stability Index
6.0 - 7.5
6.0 - 7.5
Langelier Saturation Index
-0.5 - +0.5
-0.5 - +0.5
CORROSION
Hydrogen Sulfide (H2S)
< 0.5 ppm *
10-50 ppm
Sulfates
< 125 ppm
< 125 ppm
Chlorine
< 0.5 ppm
< 0.5 ppm
Chlorides
< 20 ppm
< 150 ppm
Carbon Dioxide
< 50 ppm
< 50 ppm
Ammonia
< 2 ppm
< 2 ppm
Ammonia Chloride
< 0.5 ppm
< 0.5 ppm
Ammonia Nitrate
< 0.5 ppm
< 0.5 ppm
Ammonia Hydroxide
< 0.5 ppm
< 0.5 ppm
Ammonia Sulfate
< 0.5 ppm
< 0.5 ppm
Dissolved Solids
< 1,000 ppm
< 1,500 ppm
IRON FOULING
Iron (Fe2+ Iron Bacteria
Potential)
< 0.2 ppm
< 0.2 ppm
Iron Oxide
< 1 ppm
< 1 ppm
EROSION
Suspended Solids
< 10 ppm, < 600 μm size **
< 10 ppm, < 600 μm size **
Maximum Water Velocity
6 ft/sec
6 ft/sec
* No "rotten egg" smell present at < 0.5 ppm H2S.
** Equivalent to 30 mesh strainer
WARNING:
Field wiring must comply
with local and national electric codes.
WARNING:
Power to the unit must be
within the operating voltage range
indicated on the unit nameplate or on
the performance data sheet.
NOTE: Operation of unit on improper
line voltage or with excessive phase
imbalance will be hazardous to the unit,
constitutes abuse and may void the
warranty.