SM Series Heat Pump
SM Series Heat Pump
6 720 220 406 (2015/02)
Subject to change without prior notice
28
|
Condensate Drain
1. Remove and discard factory provided screws
from locations where hanging brackets will be
installed shown in Figure #93
Figure # 93
2. Mount 5 brackets to unit corner post using the
Bolts provided in the kit as shown on Figure # 94
Figure # 94
3. Install rubber grommet onto the brackets as
shown in Figure # 95
4. Hang the unit and assemble the field provided
Thread rod, nuts and washers on to the brackets as
shown in Figure # 95
Figure # 95
CONDENSATE DRAIN
Figure # 96
A drain line must be connected to the heat pump
and pitched away from the unit a minimum of 1/8”
per foot to allow the condensate to flow away from
the unit.
This connection must be in conformance with local
plumbing codes. A trap must be installed in the
condensate line to insure free condensate flow.
WARNING: Do not re-use screws removed
from the unit on step 1 to mount the
hanging brackets to the unit.
WARNING: Follow all applicable codes and
requirements when hanging this unit,
selecting threaded rod material, etc.
WARNING:Rods must be securely anchored
to the ceiling
When converting unit from left-hand return to
right-hand return, condensate drain connection
must be relocated. Refer to Pg#20.
HZ Heat Pump Drain Pan is not internally
sloped.