Singular Combi Boiler - BTC 439002301 A (12.2021)
8.3 A4 Error (Overheating of Heat Exchanger)
Error
Description
High Limit Cutout Error
T2: Stop the combustion when the surface temperature of the exhaust gas hood becomes higher than 302 °F due to
backfi re.
T3: Stop the combustion when the surface temperature of the heat exchanger supply pipe becomes higher than 203 °F
due to abnormal overheating.
(Operation principle: Bi-metal method, series connection)
Checkpoint
Check the connection of the overheat prevention device and wire connector.
—
Color: Red-Red
Check the connection of the high limit cutouts to the control board
Check the conduction condition of the high limit cutouts
Check if the High Limit Cutout HEX T2 (302°F) and High Limit Cutout Supply T3 (203°F) are normal
1) Check the temperature sensor resistance table
2) Check the scale on the detection part of the sensor
Table 26
Figure 13
Check the assembly condition
of the control board and the
high limit cutout connection.
Replace the high limit
cutout connection
Replace the high limit
cutout connection
Replace the control board
Check the
high limit cutout
connection
Is the
resistance of
the high limit cutout
connection
normal?
Yes
Yes
No
No
Separate the high limit cutout installed on
the heat exchanger(T2) and supply line (T3)
from the control board and check
the resistance (Normal if it is below 1 Ω)