Prerequisites for commissioning
2–4
1070 066 091-102 (01.08) GB
2.2
Configuring the PROFIBUS interface at the drive
The following settings will not be effective unless the drive has been re-
booted. Therefore, they should be made before proceeding with the com-
missioning process:
D
PROFIBUS address
D
Mode
PROFIBUS address
L
Rotary switches S2 and S3 on the individual inverters are used to set the
PROFIBUS address as a 2-digit hexadecimal value.
The value setting must be unique, i.e. it may be assigned to a single slave in
the PROFIBUS environment only.
S2
S3
Address __ __ (hex)
S2
S3
Address 02 (hex)
Example:
Baudrate
The baudrate set by the master is automatically identified by the drive.
Maximum baudrate: 12 MBaud.
Mode
L
Set rotary switch S4 to the value ”0”.
S5
Mode
0
Standard operation
F
Test mode
Connection between master and slave
L
Plug the PROFIBUS into the inverter (X51).
.
For pin assignments and wiring of the X51 PROFIBUS interface, please
refer to the annex on page A–1 ff.