Security Escort
Testing and troubleshooting | en
35
Robert Bosch (SEA) Pte Ltd
Hardware Installation Manual
2018.03 | SE3v1.0 | DOC
Symptoms
Probable Cause
Possible Solutions
Single SE receiver
intermittently not responding.
SE receiver is located past
the 1000 m (3300 ft)
maximum cable run.
Re-position the SE receiver
within the recommended
spacing. Refer to Chapter 3.
Moisture on circuit board.
Seal housing where moisture
is entering enclosure. Replace
SE receiver until the old one
dries out.
Bad splice to SE receiver.
Check all splices to make
sure cables are tight and not
loose causing high resistant
open.
Defective SE receiver.
If power is present and
address switch is configured
correctly, replace SE receiver.
SE receiver jamming.
Electrical equipment in area
causing jamming on SE
receiver.
Go to the software dialog
Setup
r
eceiver configuration
.
Increase jamming threshold
by one degree at a time until
jamming stops and SE
receiver returns to normal. If
jamming persists after
increasing level, relocate SE
receiver or attempt to identify
and minimize the jamming
source.
SE receiver LEDs not working. Defective SE receiver.
Replace the SE receiver.
SE receiver’s sounder not
operating.
Switch 6 on dip switch CFG1
in “OFF” position on SE
receiver.
Remove the cover, check dip
switch CFG1 and make sure
switch 6 is set to “ON”.
“Run Silent” is turned on in
the Central Console software.
At the Central Console, select
menu
Setup
>
Transponder
Parameter
dialog and un-
check the
Run Silent
checkbox.
Defective SE receiver.
If the sounder still does not
operate after performing the
steps above
,
replace the SE
receiver.
Tab.
6.4:
SE receiver issues