Error
Correction
No image visible
●
Connect the supply voltage, check the X1S1 connection
●
Connect the CDI cable correctly, check XVID and XSER
●
Set the screen output in the graphics driver to "VDP"
●
Switch on the voltage at the VDP before or at the same
time as the control cabinet PC
Distorted display due to incorrect dis-
play resolution
●
Set the correct display resolution in the graphics driver
●
Restart the control cabinet PC
The USB flash drive does not function,
although other USB devices function
●
Set the DIP switch on the VDP to <30 m
●
Note: USB flash drives can only be used up to a cable
length of 30 meters
USB devices and touch screen do not
work
●
Set the DIP switch according to the cable length.
Tab. 13-1: Error causes and error elimination
14 Maintenance
14.1 General Information
Loss of IP degree of protection due to incorrect
maintenance.
NOTICE
The IP degree of protection must be ensured during maintenance!
14.2 Display
The backlight is subject to wear, see
chapter 5.5 "Wear Parts" on page 7
A fading backlight causes a progressive deterioration display readability, so that
a replacement is necessary. For further information please contact the Bosch
Rexroth Service.
14.3 Cleaning Notes
Disintegrating of face-plate sealing due to sol-
vent!
NOTICE
●
Do not use solvents.
●
Do not use high pressure cleaning devices.
VDP 15.3, 18.3, 21.3 Multitouch
Bosch Rexroth AG
Maintenance
DOK-SUPPL*-VDPXX.3MTBU-IT02-EN-P