In operation
Transport
Storage
Humidity
Min. relative humidity:
5 %
Max. relative humidity:
85 %
Min. absolute humidity:
1 g/m
3
Max. absolute humidity:
25 g/m
3
Condensation not al-
lowed
Corresponds to climatic
class 3K3 acc. to EN
60721-3-3
Min. relative humidity:
5 %
Max. relative humidity:
75 %
Min. absolute humidity:
1 g/m
3
Max. absolute humidity:
25 g/m
3
Condensation not al-
lowed
Corresponds to climatic
class 2K2 acc. to EN
60721-3-2
Min. relative humidity:
5 %
Max. relative humidity:
85 %
Min. absolute humidity:
1 g/m
3
Max. absolute humidity:
25 g/m
3
Condensation not al-
lowed
Corresponds to climatic
class 1K2 acc. to EN
60721-3-1
Air pressure
Up to 3000 m above sea
level acc. to EN
61131-2
Up to 3000 m above sea
level acc. to EN
61131-2
Up to 3000 m above sea
level acc. to EN
61131-2
Mechanical strength
Max. vibration:
Frequency range: 10 Hz
to 150 Hz
Excursion: 0.075 mm at
10 Hz to 57 Hz
Acceleration: 1 g at
57 Hz to 150 Hz
acc. to EN 600068-2-6
Max. shock:
15 g 11 ms
acc. to EN 60068-2-27,
no disturbance of the
function
Max. shock:
15 g 11 ms
acc. to EN 60068-2-27,
no disturbance of the
function
Contamination level
2
2
2
Overvoltage category
2
-
-
Tab. 6-1: Ambient conditions
The ambient air must not contain acids, alkaline solutions, corrosive
agents, salts, metal vapours, and other electrically conductive con-
taminants in high concentrations.
The ambient air must be dust-free. Housing and installation compart-
ments must at least comply with degree of protection IP 54 accord-
ing to DIN VDE 0470-1.
Bosch Rexroth AG
Ambient Conditions
VDP 15.3, 18.3, 21.3 Multitouch
8/37
DOK-SUPPL*-VDPXX.3MTBU-IT02-EN-P