10.6.3 Connection Scheme – Power Supply Unit, UPS, Control Cabinet
PC and Operating Display
X10
UPS
230 V
24 V
24 V
24 V
Out
24 V
In
230 V ~
+
-
+
-
U
+
-
+
-
1
2
3
USB cable
X1S1/2 (GND)
X1S1/1 (24VDC)
XSER
XVID
XSER
XVID
Operator display
XUSBIN, type B
XUSB1..6
XUSB1...4
Front panel
USB connection
USB connection
Type B
USB connection
Type A
for USB2.0, max. 5 m
Control cabinet PC
External power
supply unit
(as option)
Fig. 10-10: Connection scheme — power supply unit, UPS, control cabinet PC and operating
display
10.6.4 Recommendation for the Assembly of CDI Cables with Long
Lengths in an Interference-Prone Environment
General Information
The CDI cable is a connection cable with RJ45 connector to connect the CDI in-
terface of the control cabinet PC to the remote operating display or the Y-re-
peater.
These assembly instructions facilitate an optimized signal transmission. In par-
ticular in case of long cable lengths and great distances between the control
cabinet PC and the remote operating display, make sure that the cable is instal-
led correctly and the shield is connected correctly.
Laying the Cables
Refer to the following information regarding the cable installation:
●
Keep the maximum possible distance to interference-prone cables and lines
●
Limit parallel routing with other lines
●
Keep the maximum possible distance to sources of interference such as
drives and frequency converters
●
Mechanical protection against tensile load and compressive load on the cable
●
Comply with the permissible bending and torsional stress of the cable
●
Avoid collection of dirt at the R45 connector which can occur during drawing
in of the cables in the installation.