X10
control cabinet PC
UPS
230 V
→
24 V
24 V
24 V
24 V
230 V ~
+
+
U
+
+
1
2
3
USB connection
type B
USB connection
USB cable
X1S1/2 (0 V)
X1S1/1 (24 VDC)
XSER
XVID
XSER
XVID
operator display
XUSBIN
XUSB1..6
XUSB1...4
Front USB connection
for USB2.0
External
Out
In
type A
–
–
–
–
1
VDP xx.3
(as option)
power supply unit
①
chapter "Operation Modes" on page 46
section "Distance between
control cabinet PC and VDP max. 5 m".
Fig.7-5:
Voltage supply and optional USB2.0 port
7.2.5
XUSB Interfaces
The devices are provided with four USB interfaces on the connector panel
(XUSB1/2 and XUSB3/4) and - depending on the variant - one USB interface
on the front panel.
Switching off of the VDP power supply unit if
the total current of all USB female connectors
exceeds 1 A.
NOTICE
The maximum power consumption of one USB connector must not exceed 500
mA. The total current of all USB female connectors must not exceed 1 A.
Fig.7-6:
USB interfaces XUSB1/2 and XUSB3/4
Operating the USB connections on
the VDP 16.3/40.3 in the USB2.0
mode
The USB connections on the VDP 08.3/40.3 only support USB1.1 because the
data is transferred to the control cabinet PC by using the XSER interface. The
XUSB1 to XUSB6 connection on the control cabinet PC support USB2.0. If
USB2.0 is also required on the VDP 08.3/40.3, it can be implemented by con‐
necting the XUSBIN connection to the VDP 08.3/40.3 to one USB connection
(XUSB1 up to XUSB6) of the control cabinet PC by using an USB cable (see
fig. 7-5 "Voltage supply and optional USB2.0 port" on page 48
). The USB cable
can be ordered as accessory, see
chapter 12.2.5 "Connecting Cable for USB
.
Bosch Rexroth AG
DOK-SUPPL*-VDP*08.3***-PR02-EN-P
Rexroth IndraControl VDP 08.3/40.3 Operator Terminal
48/81
Interfaces