7
Interfaces
7.1
View on the Connector Panel
Fig.7-1:
Connector panel of the VDP 40.3, inner side
7.2
Interfaces at the VDP
7.2.1
General Information
Malfunctions due to insufficient shielding!
NOTICE
Use only shielded cables and metallic or conductive connector/coupling covers
with large-area shield support.
Material damages to electronics due to missing
functional earth ground connection!
NOTICE
Please ensure that the functional earth ground is connected, because other‐
wise the electronics can be destroyed by a potential difference between the
VDP 08.3/40.3 and the PC if the voltage supply is interrupted to only one device
and established again.
7.2.2
Overview
Designa‐
tion at the
housing
Connection type
Connector type (in‐
tegrated)
Mating connector or
cable (from outside)
X1S1
DC 24 V power supply
Phönix connector
strip,
3-pin,
MC1,5/3-
G-3,5THT
Phönix female con‐
nector strip,
3-pin,
FK-MCP
1,5/3-ST-3,5
XUSB1/2
2 USB interfaces
USB female con‐
nector, 4-pin, type A
USB connector, 4-
pin, type A
XUSB1/4
2 USB interfaces
USB female con‐
nector, 4-pin, type A
USB connector, 4-
pin, type A
XSER
CDI interface, data
RJ45 female con‐
nector
RJ45 connector
DOK-SUPPL*-VDP*08.3***-PR02-EN-P
Rexroth IndraControl VDP 08.3/40.3 Operator Terminal
Bosch Rexroth AG
45/81
Interfaces