Fig.7-5:
Limit values of the DC 24 V voltage
Wiring 230 V
PE
PE
PE
PE
PE
PE
PE
(1)
6 mm² (green/yellow)
16 mm² (green/yellow)
min. 16 mm² (green/yellow)
PE neutral point
230V
400V
4 mm² (green/yellow)
Fuses, better: protective motor switches
16 mm² (green/yellow)
4 mm² (green/yellow)
Overvoltage category III
e.g. drives
W1
N
V1
U1
L1 L2 L3 N
Leads
L1.1
L2.1 L3.1 N
PE
PE
N
U2
PE
N1 U2
4 mm² (green/yellow)
Power unit
VAP01.1H-W23
024-010-NN
Overvoltage category I
(1)
PE
N1
U2
Power unit
VAP01.1H-W23
024-010-NN
U
L
U
L
0 V
0 V
U
Q
U
Q
DC 24 V
DC 24 V
N-conductor:
Use only with
permission of
the operator!
Transformer
acc. to EN 60742
All housing parts (functional ground)
To the machine
To the housing of the control cabinet
Overvoltage category II
230 V power supply
operator terminals
service plug receptacle(s)
Terminals in
isolated
arrangement
PE bars are to be installed preferably on the mounting plate.
In case of isolated PB bars, both ends must be connected to the mounting plate
by means of copper strips with a maximum length of 20 cm.
The cross-section of the copper strips has to be at least equal to that of the incoming cable.
Fig.7-6:
Wiring 230 V
Danger of death by high electric voltage
DANGER
●
Connect power supply units, which generate protective extra-low voltage
(PELV) (24 V), only to supply voltages for which they are designed. Do
observe the overvoltage categories, see also
●
Do not apply the supply voltage to the protective extra-low voltage (PELV).
DOK-SUPPL*-VAM*XX.1***-PR02-EN-P
Rexroth IndraControl VAM 12.1/42.1 Machine Control Panels
Bosch Rexroth AG
55/93