Rexroth EcoDrive 03 DKC**.3-016
Instructions for Use
5-5
DOK-ECODR3-DKC16*UL***-IB01-EN-P
Input voltage:
High
Low
min.
16 V
-0.5 V
max.
30 V
3 V
Input resistance
13.3 kOhm ±5%
Reaction time
See functional firmware description
Fig. 5-9:
Inputs
The drive halt function is used to bring an axis to standstill with defined
acceleration and jerk (see functional firmware description).
The input drive enable (RF) activates the drive with a 0-1 edge.
Note:
If the inputs are controlled by a power supply other than the
DC24 volt supply of the DKC, then the reference lead of the
other power supply must be connected to X1.2 (0 V).
Ready to operate contact Bb
AP5394f1.FH7
X1
2
5
1
3
4
6
Bb
Bb
ready for operation
device-external
device-internal
ready for operation
Fig. 5-10:
Connections for ready to operate contact
Max. switching voltage:
DC 40 V
Max. switching current:
DC 1 A
Max. continuous current:
DC 1 A
Minimum contact load:
10 mA
Guaranteed number of switching operations
at max. time constant of load < 50 ms:
250,000
The Bb contacts opens:
•
if control voltage for DKC is not applied
•
if 24 volts not present at the emergency stop input when the E-stop
function is activated (depends on parameterization, see function
description).
•
With an error in the drive (depends on parameterization, see functional
firmware description: "Power off on error").
WARNING
Damage possible if Bb contact not connected !
The ready to operate contact Bb acknowledges the drive
is ready for mains voltage.
⇒
Integrate Bb contact as per "Control Circuits for the
Mains Connection" (see Project Planning manual).
⇒
The evaluation of the Bb contact by a PLC may not
cause any operating delay of more than 10 ms.
Inputs
AH and RF:
AH:
RF:
Connection
Bb:
Loadability of the connection
Bb:
Switching states
Bb: