5-6
Instructions for Use
Rexroth EcoDrive 03 DKC**.3-016
DOK-ECODR3-DKC16*UL***-IB01-EN-P
Connection of Control Interfaces and Terminals
See Project Planning Manual for more details.
X5, Motor and Mains Connections
DANGER
Lethal electric shock caused by live parts with
more than 50 V!
⇒
Before working on the drive controller, switch off the
power supply via the main switch or the fuse.
⇒
Always mount or dismount both connectors (motor
connector and mains connector) on the drive
controller at the same time.
⇒
Connect the protective conductor connections XE1
and XE2 to the protective conductor system of the
control cabinet. Check the continuity of the protective
conductors from the mains connection to the
connected motors.
⇒
Observe information in chapter "Important Notes"
Technical description of connector
Ap5402f1.fh7
barbs
Fig. 5-11:
Connector X5
Note:
•
To pull off the connectors, loosen the barbs.
•
The maximum number of insertion/withdrawal cycles is
limited to 15.
Type
No. of pins
Design
connection block
2 x 3
bushing on connector
Fig. 5-12:
Design
Cross section
single wire
[mm²]
max. connectable
cross section
[mm²]
max. Wire size
in AWG
gauge no.:
1,5
1,5
16
Fig. 5-13:
Connection cross section
Illustration:
Design:
Connection cross section: