22 / 50
ctrlX CORE X7
Interface description
Bosch Rexroth AG
R911419122, Edition 01
EtherCAT process data
The bus coupler and the ctrlX CORE are provided with data that is inserted into the cyclic process
image. This data length is 5 words in total. According to the EtherCAT standard, this data before the
input process data is shown in the process image.
The process data words 0...3 contain the voltage and current values of U
P
and U
L
(only the current
consumption of the infeed terminal and the I/O modules) as well as their bits for the supply voltage
diagnostics. This information can also be retrieved via acyclic services using CoE. These are shown as
the indices 6000, 6010 and 6020 hex.
Word 0
U
P
Voltage
Word 1
U
P
Current
Word 2
U
L
Voltage
Word 3
U
L
Current
(Only the current consumption of the infeed terminal (typ. 50 mA) and the
I/O modules (3 A max.) is measured. In addition to the transferred measured
value, the ctrlX CORE
PLUS
consumes more than shown here.
Word 4
0
1
2
3
4
5
6-15
U
P
Undervoltage
U
P
Overvoltage
U
P
Overcurrent
U
L
Undervoltage
U
L
Overvoltage
U
L
Overcurrent
Reserved
Diagnostic strategy
Mechanisms
Different mechanisms are used for the diagnostics.
Mechanism
Diagnostics
EtherCAT state machine
EtherCAT hardware watchdog
EtherCAT system diagnostics
Diagnostic objects in the CoE object directory
10F1
Extended diagnostics, e.g. peripheral errors
Error settings
Diagnosis history object
10F3
20 diagnostic messages can be stored
Diagnosis history