13 / 50
ctrlX CORE X7
General technical data
Bosch Rexroth AG
R911419122, Edition 01
Broadband noise acc. to DIN EN 60068-2-64
5-20-150 Hz with 0.572 g, 5 h per axis
Electrostatic discharge
ESD resistance acc. to DIN EN 61131-2
•
Test voltage
Criterion B
8 kV for air discharge
4 kV for contact discharge
①
To avoid vibration, secure the cables at a short distance (< 20 cm).
NOTICE
Failure of the product due to contaminated air!
−
The ambient air must not contain acids, alkaline solutions, corrosive
agents, salts, metal vapors and other electrically conductive contami-
nants in high concentrations.
−
The devices to be installed into the housing and installation compart-
ments must at least comply with the degree of protection IP
54
according to DIN EN 60529.
−
The device shall be provided in a suitable fire enclosure in the end-use
application.
NOTICE
Defective product due to gases jeopardizing functions
Due to the risk of corrosion, avoid sulphurous gases (e.g. sulphur dioxide
(SO
2
) and hydrogen sulphide (H
2
S)). The product is not resistant against
these gases.
NOTICE
Failure of the product due to overheating
To avoid overheating and to ensure a smooth operation of the product,
sufficient air has to circulate according to the minimum distances specified,
see
This is a product that corresponds to the limit values of the emitted interference of class A
(industrial environments). This is a product that does not correspond to the limit values of the
emitted interference of class B (residential area and small enterprises.
When using the product in residential areas or small enterprises, the operator has to take
actions to prevent radio interferences (also refer to DIN EN 55022).
7
Technical data
7.1
General technical data
COREX-M-X7
Processor
11th Generation Intel® Core™/I7 Quad Core Processor
RAM
16 GByte DRAM
Internal physical read-only memory
(eMMC)
32 GByte, also refer to
Internal non-volatile random-access
memory (NVRAM)
2 Mbyte
Extensions
Onboard functions and ctrlX I/O modules
Tec
hnical dat
a