ctrlX CORE X7
Housing dimensions
Bosch Rexroth AG
R911419122, Edition 01
Diagnosis history 10F3
hex
The object 10F3hex is implemented as ring memory into the "Overwrite mode". The latest 20 diag-
nostic messages are stored. Older messages are deleted.
The following table shows the structure of a diagnostic message for EtherCAT.
Index (hex)
Subindex
Object name
Data type
Length
Rights
Meaning
10F3
Diagnosis history
Diagnostic statistics
01
Maximum messages
UINT8
1
R
Maximum number of messages
02
Newest message
UINT8
1
R
Latest message
03
Newest acknowledged mes-
sage
UINT8
1
R/W
Latest confirmed message. Writing "0"
deletes the messages in the ring
memory.
04
New messages available
Boolean
0.1
R
New message available
05
Flags
UINT8
2
R/W
Setting of the object response. Refer to
ETG.1020
10
Mounting, dismounting and electric installation
10.1 Housing dimensions
160
105
126
6
Fig. 5: Front view
Mounting, dismounting and electr
ic ins