47.3.5 Start
The
Start
action is intended for making emergency calls
for phased evacuation. The
Start
action starts a call,
based on a call macro, in a pre-defined zone or zone
group. The priority of the call is the same as the priority
of the call macro and cannot be changed. See figure
47.12 for an overview of the
Action programming
page for
a
Start
key.
If more than one action (up to a maximum of 5) is
configured for a
Start
key or control input, see section
43.2.5, then also multiple sets of
Call macro
and
Zones
can be configured here.
Typically, there will be multiple
Start
actions that use
the same call macro, but address other zones or zone
groups. In case of a phased evacuation, the different
Start
actions then can be used to expand the area in
which the call is running.
When the activator of a
Start
action is released, the
running call is stopped in the zones or zone groups that
are associated to the action. In case of a phased
evacuation, releasing the different
Start
actions can be
used to reduce the area in which the call is running.
47.3.6 Stop
The
Stop
action is intended for aborting emergency calls
for phased evacuation. The
Stop
action aborts all calls
that are based on the defined call macro. See figure
47.13 for an overview of the
Action programming
page for
a
Stop
key.
If more than one action (up to a maximum of 5) is
configured for a
Stop
key or control input, see section
43.2.5, then also multiple
Call macros
can be configured
here.
figure 47.12: Start action key
figure 47.13: Stop action key