1 1 6 |
Bosch Geothermal Heat Pumps
Bosch Thermotechnology Corp.
Data subject to change
Applications Manual
17.6 Differential Pressure Switch
Speci c models of 208/230V Bosch geothermal heat
pumps may be equipped with a factory installed
Differential Pressure Switch (DPS). The DPS prevents
compressor operation if there is inadequate water ow
(gallons per minute) through the geothermal heat pump
water to refrigerant heat exchanger.
The DPS operates by monitoring the water side pressure
drop across the water to refrigerant heat exchanger. When
the pressure drop between the water in and water out
lines reaches a pre-set value, compressor operation is
enabled.
Fig. 141 Differential Pressure Switch (actual design may differ)
17.7 Electric Heat
Internally mounted supplemental electric heat is an
available option for speci c models of 208/230V Bosch
geothermal heat pumps. Electric heating elements can
operate along with reverse cycle heating as auxiliary heat
or in lieu of mechanical heating (refrigeration heating) as
emergency backup heat. Heating elements are available
in nominal kW ranges of 5, 10, 15 and 20 - note that
not all sizes are available on all models. Internal heat is
only available on top blow vertical cabinets, end blow or
straight through blow horizontal cabinet or on down blow
counter ow cabinets. Always refer to the speci c model
installation manual for heater selection.
Internal electric heat cannot be provided with hot gas
reheat. Units with internal electric heat must have 2 eld
power supplies.
Fig. 142 Electric Heat
17.8 Sound Package
Speci c models of 208/230V Bosch geothermal heat
pumps may be equipped with a factory installed sound
reduction package option. This option improves the
already industry leading noise levels of the heat pump
by adding a heavy duty, multi density blanket over the
compressor. The materials in the blanket are engineered
to attenuate the most objectionable frequencies of sound
coming directly off of the compressor shell, further
reducing the operating noise of the heat pump.
F
ig. 143 Sound Package
17.9 Soft Start (SecureStart™)
Speci c models of 208/230V Bosch geothermal heat
pumps are available with the SecureStart™ start assist
device as either a factory installed option or a eld
installed accessory. This device reduces starting current
for compressors by 25 to 60%. This reduction in starting
current can eliminate or greatly reduce "light icker"
during compressor starts and can reduce the required
size of back-up transformers. The adaptive technology of
the device can also extend compressor life by providing
smoother, lower current starts and by protecting the
compressor from transient low voltage. Over time
SecureStart™ self-adjusts to motor starting current
thereby eliminating any manual calibration.
F
ig. 144 Soft Start (SecureStart™)